Johnson Controls Unitary Products
49
XP036-060 Side Duct Application
ZR036 - 060 (3-5 Ton Direct Drive) Bottom Duct
UNIT
TONNAGE
MOTOR
1
SPEED
1. Factory set on medium speed tap.
AVAILABLE EXTERNAL STATIC PRESSURE - IWG
2
2. Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to STATIC RESISTANCES Table for
resistance values.
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
CF
M
W
A
TTS
CF
M
W
A
TTS
CF
M
W
A
TTS
CF
M
W
A
TTS
CF
M
W
A
TTS
CF
M
W
A
TTS
CF
M
W
A
TTS
CF
M
W
A
TTS
CF
M
W
A
TTS
3
3
3. Bottom Duct application (230 Volts)
HI
1520
320
1478
335
1438
349
1401
363
1363
376
1327
390
1286
403
1248
417
1207
430
MED/HI
1430
263
1384
276
1342
290
1302
303
1259
316
1215
329
1168
343
1114
358
1044
374
MED
1287
208
1242
221
1199
234
1155
246
1108
258
1060
272
997
288
930
303
889
313
MED/LOW 1185
171
1138
183
1091
195
1041
207
987
220
921
235
862
248
-
-
-
-
LOW
1040
130
959
134
900
145
-
-
-
-
-
-
-
-
-
-
-
-
4
HI
-
-
1995
696
1957
714
1922
734
1885
749
1844
764
1795
769
1709
743
1566
685
MED/HI
1846
539
1812
557
1776
571
1736
585
1704
602
1662
619
1619
638
1566
653
1492
639
MED
1662
408
1624
426
1577
438
1542
455
1501
472
1454
490
1400
505
1356
521
1323
536
MED/LOW 1566
362
1526
380
1480
391
1450
406
1411
423
1363
440
1312
455
1279
469
1235
485
LOW
1287
223
1246
237
1190
247
-
-
-
-
-
-
-
-
-
-
-
-
5
HI
2166
883
2169
931
2158
950
2134
964
2095
979
2040
971
1963
940
1881
898
1791
854
MED/HI
2060
771
2042
784
2035
808
2006
826
1970
844
1934
859
1888
861
1821
843
1730
806
MED
1940
637
1920
656
1907
675
1870
696
1834
715
1802
730
1759
740
1722
756
1657
748
MED/LOW 1688
413
1645
432
1611
451
1575
468
1534
479
1498
497
1461
513
-
-
-
-
LOW
1509
327
1477
339
-
-
-
-
-
-
-
-
-
-
-
-
-
-
XP036 (3 Ton Belt Drive) Side Duct
Air Flow
(CFM)
Available External Static Pressure - IWG
1
1. Blower performance includes 1” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
4. Field Supplied Drive.
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Field Supplied Drive
Standard Drive Option
HIgh Static Drive Option
800
678
0.37
761
0.44
840
0.52
917
0.60
991
0.69
1062
0.77
1130
0.87
1195
0.96
1259
1.06
1320
1.17
1000
699
0.42
782
0.49
862
0.56
939
0.64
1012
0.73
1083
0.82
1151
0.91
1217
1.01
1280
1.11
1341
1.21
1200
727
0.45
810
0.52
889
0.60
966
0.68
1040
0.76
1110
0.85
1179
0.95
1244
1.04
1308
1.14
1369
1.24
1400
759
0.51
842
0.58
922
0.65
998
0.73
1072
0.82
1143
0.91
1211
1.00
1276
1.10
1340
1.20
1401
1.30
1600
795
0.60
878
0.67
958
0.74
1035
0.82
1108
0.91
1179
1.00
1247
1.09
1313
1.19
1376
1.28
1438
1.39
FS
4
XP048 (4 Ton Belt Drive) Side Duct
Air Flow
(CFM)
Available External Static Pressure - IWG
1
1. Blower performance includes 1” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Field Supplied Drive
Standard Drive Option
HIgh Static Drive Option
1000
699
0.42
782
0.49
862
0.56
939
0.64
1012
0.73
1083
0.82
1151
0.91
1217
1.01
1280
1.11
1341
1.21
1200
727
0.45
810
0.52
889
0.60
966
0.68
1040
0.76
1110
0.85
1179
0.95
1244
1.04
1308
1.14
1369
1.24
1400
759
0.51
842
0.58
922
0.65
998
0.73
1072
0.82
1143
0.91
1211
1.00
1276
1.10
1340
1.20
1401
1.30
1600
795
0.60
878
0.67
958
0.74
1035
0.82
1108
0.91
1179
1.00
1247
1.09
1313
1.19
1376
1.28
1438
1.39
1800
836
0.72
919
0.79
999
0.87
1075
0.95
1149
1.03
1220
1.12
1288
1.22
1353
1.31
1417
1.41
1478
1.51
2000
880
0.89
963
0.96
1042
1.04
1119
1.12
1193
1.20
1263
1.29
1331
1.39
1397
1.48
1460
1.58
1522
1.68