Connections for single hardwire output with gfci, Warning: shock hazard – Xantrex Technology PROsine 2.0 User Manual
Page 58
Installation
3–16
445-0089-01-01
Connections for Single Hardwire Output With GFCI
Figure 3-6 is a cutaway top view of the PROsine wiring compartment showing
one set of outgoing AC wires with the GFCI option.
To make the AC output wiring connections
1. Run 10AWG 2-conductor-plus-ground through one of the cable clamps on the
AC end.
2. Strip about two inches of the jacket from the AC cable and separate the wires.
Strip insulation from each of the wires according to the guidelines given by
the connector manufacturer.
3. Connect the outgoing black and white (line and neutral) AC wires to the
PROsine black and white AC output wires.
4. Connect the outgoing ground wire to the chassis using one of the screws
marked .
5. Tuck the wires into the left-hand side of the wiring compartment so they don’t
interfere with the GFCI assembly.
WARNING: Shock hazard
If you are not using the hardwire output circuit, you must cap off its line and neutral wires.
Use twist-on wire nuts where allowed; use crimp-on wire caps in other applications.
Figure 3-6 Single Hardwire Output With GFCI
grounding screw
Cutaway view of
PROsine 2.0 wiring
compartment as
seen from the top.
Do not
disturb
factory
wiring.
GFCI
wire nuts or crimp-on
wire caps (depending
on type of installation)
outgoing
AC cable