Step 6: Connecting the AC Output Wires
445-0089-01-01
3–15
Step 6: Connecting the AC Output Wires
Two options are available for AC output wiring:
•
Hardwire output.
•
Single hardwire output plus GFCI receptacle.
Connections for Hardwire Option
To make the AC output wiring connections
1. Run 10AWG 2-conductor-plus-ground cable through one of the cable clamps
on the AC end.
2. Strip about two inches of the jacket from the AC cable and separate the three
wires. Strip insulation from each of the wires according to the guidelines
given by the connector manufacturer.
3. Connect the outgoing black and white (line and neutral) AC wires to the
PROsine AC output black and white wires.
4. Connect the incoming ground wire to the chassis using one of the screws
marked .
5. Connect the outgoing AC wires to an AC load panel equipped with circuit
breakers.
Figure 3-5 Hardwire AC Output Option (Top, cutaway view of wiring
compartment)
Cutaway view of
PROsine wiring
compartment as
seen from the top.
wire nuts or crimp
connections (depending
on type of installation)
clamp
for AC cable
grounding screw
AC cable