Xantrex Technology PROsine 2.0 User Manual
Page 56
Installation
3–14
445-0089-01-01
The PROsine is shipped with the screw in the position that enables the automatic
bonding system.
•
To disable the system, move the screw to the other hole.
•
Do not remove the screw from the product: make sure it is always installed in
one position or the other, as appropriate for the configuration of the rest of the
system.
Table 3-4 AC Output Neutral-to-Ground Bonding Screw Settings
Bonding Screw
Setting
Status of Bonding
Internal to the PROsine
Neutral Bonding Required
External to the PROsine
AC shorepower not
present (unit Inverting
or in Standby)
AC shorepower present
(unit Charging or in
Standby)
In the AC input
shorepower
source
In the AC load
panel
Automatic
bonding
Output neutral bonded
Output neutral
un-bonded
Yes
No
Un-bonded in
all modes
Output neutral un-
bonded
Output neutral un-
bonded
No
Yes