SERVICE TECHNICIAN ONLY — read and follow completely.

Manual reset

temperature switch

Thermostat

44156

Close clearance installation

Substitute these instructions for corresponding material in

manual. All other procedures and practices must remain the same.

Recommended service and minimum clearances shown on

page 8 should be used where possible. Where closer clearances

are required:

• Top of boiler — If less than 24" available, provide removable

surface to allow for cleaning boiler flueways.

• Right or left side — Minimum 2 inches.
• Front — Minimum 2 inches from burner.
• Double-wall flue pipe to combustible surface — as listed in

Table 5, page 33

and Figure 24 through Figure 26, page 33.

Jacket cap must be in place on boiler to avoid requir-

ing an 9" minimum clearance from back or top of

boiler to combustible material. Flue pipe clearances

must take precedence over jacket clearances.

1. Install boiler using clearances described at left.
2. Install barometric control 18-20 inches from boiler in

breeching.

3. Attach manual reset temperature switch near upper surface

of enclosed area. See Figure 22.

4. Wire switch in series with thermostat. See Figure 23.
5. Provide two combustion/ventilation openings when install-

ing in confined space. Size opening 140 sq. in. (1000 Btu)

per 1 GPH input. Locate openings near top and bottom of

enclosed space.

Burner adjustments for packaged and

non-packaged boilers

Final burner adjustments must be made using com-

bustion test equipment to assure proper operation.

Do not fire boiler without water or sections will

overheat.

1. Refer to burner manual for start-up.
2. Allow boiler to heat to design condition.
3. Using combustion test equipment, adjust burner for:

a. CO2 between 11% and 12% and 0 smoke.
b. -0.01” to -0.02” W.C. draft in combustion chamber.

To provide close clearances as described on pages 26 and 27:

Obtain the Close Clearance Kit, Weil-McLain Part No. 386-500-050. Install the kit as described below. Failure to use

kit or install as described can result in a fire hazard, causing severe personal injury, death or substantial property

damage.

Figure 23

Manual reset temperature switch wiring

Area above boiler

Bracket

1 to 5

inches

Manual reset

temperature

switch

Figure 22

Manual reset temperature switch location

Combustible surface

#6 X ½" Phillips

Sheet metal

screw

#10 X ½" Phillips

sheet metal screw

Close clearance installation

Part number 550-141-826/1211

32

GOLD

WGO