SERVICE TECHNICIAN ONLY — read and follow completely.

Perform hydrostatic pressure test

1. See Figure 5 and Control Tapping table to install:

a. Boiler drain.
b. Water pressure gauge (test only). Be sure gauge can

handle test pressure.

c. Air vent in upper “N” tapping.
d. Plugs in remaining tappings.

2. Fill boiler. Vent all air. Pressure test boiler at 1 times work-

ing pressure. For boilers split and reassembled, test between

75 and 85 psig.

Do not leave boiler unattended. Cold water fill

could expand and damage cast iron, resulting in

severe personal injury, death or substantial prop-

erty damage.

3. Check for maintained gauge pressure for more than 10 min-

utes. Visually check for leaks if gauge pressure drops.

4. Drain boiler. Repair leaks if found.

Do not use petroleum-based compounds to repair

leaks. Damage to system components can result,

causing property damage.

5. Re-test boiler after repairing leaks.
6. Remove pressure gauge, air vent and plugs from tappings

used for controls.

Figure 5

Control tapping locations

Front section

E3

R1

C

L

B1

H

N

Location

Size

Function

B1

1½"

Return piping

B2

1½"

Alternate return piping for

A/B WGO

C

1½"

Supply piping

E3

1/4

"

Pressure-temperature

gauge

H

¾"

Drain valve

L

¾"

High limit control

N

½"

Air vent or expansion

tank piping

R1

¾"

Relief valve

Table 2

Control tappings

B2

Back section

Install boiler — non-packaged boilers only

(continued)

7. Visually check:

a. Sealing rope placement.
b. Metal-to-metal contact around port openings.
c. Flue collector hood seal.
d. Burner mounting door seal.

Obtain gas-tight seal to prevent possible flue gas

leakage and carbon monoxide emissions, which

can lead to severe personal injury or death.

Install jacket

(sizes 7 through 9 only)

Before installing jacket, remove burner mounting door. See jacket

instructions for details.

Install boiler controls

See Control Tapping Table and Figure 5 and Figure 6, page 15

to install controls.

1. Install limit control. If not furnished, use high limit with

maximum 220°F setting.

2. Affix CP number label(s) on jacket front panel.

Part number 550-141-826/1211

14

GOLD

WGO

OIL-FIRED NATURAL DRAFT WATER BOILER — SERIES 3 —

Boiler Manual