SERVICE TECHNICIAN ONLY — read and follow completely.

Install boiler — packaged boilers only

Place boiler

1. Remove circulator strapped to pallet.

Circulator will be damaged if not removed before boiler is

lifted from pallet.

2. Remove boiler from pallet.

Do not drop boiler or bump jacket on floor or pallet. Damage

to boiler can result.

Smaller sized boilers may be top heavy. Use caution when

handling to avoid minor personal injury or property damage.

3. Boiler is shipped for back flue outlet. To change to top flue outlet (see

Figure 3, page 11):
a. Remove jacket cap on top of boiler.
b. Loosen two screws holding flue cap strap to collector hood. Remove

strap and flue cap from opening. Re-tighten screws.

c. Check rope placement inside flue cap.

(Read

under step #6 below).

d. Loosen two screws on back flue outlet. Set flue cap on outlet. Install

strap by engaging slots in screws. Tighten screws. Make sure cap is

securely installed.

e. Snap jacket cap in back outlet opening.

Jacket cap must be in place on boiler to avoid requiring an 18”

minimum clearance from back or top of boiler to combustible

material.

4. Check level. Shim legs, if needed.
5. Check for secure placement of insulation on target wall, chamber floor

and burner door.

6. Visually check:

a. Flue collector hood seal.
b. Burner mounting door seal.

Obtain gas-tight seal to prevent possible flue gas leakage

and carbon monoxide emissions, which can lead to severe

personal injury or death.

Perform hydrostatic pressure test

1. Remove relief valve installed in boiler.

2. Install air vent in “N” tapping on top boiler.

3. Plug supply and return tappings.

4. Drain valve is already factory-installed.

5. Fill boiler. Vent all air. Pressure test boiler at 1½

times working pressure.

Do not leave boiler unattended. Cold

water fill can expand and damage cast

iron, resulting in severe personal injury,

death or substantial property damage.

6. Check for maintained gauge pressure for more

than 10 minutes. Visually check for leaks if gauge

pressure drops.

7. Drain boiler. Repair leaks if found.

Do not use petroleum-based sealing

compounds to repair leaks. Damage to

system components can result, causing

property damage.

8. Retest boiler after repairing leaks.

9. Remove air vent and plugs. Reinstall relief valve.

Part number 550-141-826/1211

10

GOLD

WGO

OIL-FIRED NATURAL DRAFT WATER BOILER — SERIES 3 —

Boiler Manual