beautypg.com

Annual service check list, Boiler manual – Weil-McLain 550-141-826/1201 User Manual

Page 29

background image

SERVICE TECHNICIAN ONLY — read and follow completely.

Annual service check list

Annual Service Call

Checklist

(follow in order listed below)

Dates

Comments

1

Check that boiler area is free from

combustible materials, gasoline and

other flammable vapors and liquids.

2

Check for and remove any obstruction

to combustion and ventilation air flow

to boiler.

3

Check breeching and chimney or vent

for obstructions, damage, etc. Repair

or replace as necessary.

4

Clean boiler flueways. See Fig-

ure 21, page 30.

5

Perform service on relief valve and

circulator. See page 30.

6

Check boiler and piping for leaks and

repair if found. Check for leaks at

tankless heater plate. Tighten nuts only

if leaks are found (for WGO torque to

20-25 ft.lbs.).

7

Inspect and adjust burner. See burner

manual and:
• change nozzle.
• check ignition electrode settings.
• clean blower housing and wheel.
• make sure blower wheel turns

freely.

• oil burner motor if required.
• clean air inlet.
• clean or change fuel filter and

strainer.

8

Make sure boiler is filled with water.

9

Start unit and verify combustion set-

tings with combustion test equipment.

See page 28.

10

Verify operation of all controls on

boiler. See page 28.

Any parts of the boiler furnished by Weil-McLain must be replaced by parts listed in Weil-McLain Boiler and Repair Parts Book.

Controls requiring annual service

Water Relief Valve

Check operation of water relief valve.

Follow instructions on label fastened to

relief valve.

Scald potential. Do not check

operation of relief valve un-

less discharge piping has

been installed according to

Boiler Manual. If piping is

not in place, a qualified ser-

vice technician must prop-

erly install piping.

Circulator

Follow oil-lubricating instructions on cir-

culator. Over-oiling will damage circulator.
Water-lubricated circulators do not need

oiling.

Part number 550-141-826/1211

29

GOLD

WGO

OIL-FIRED NATURAL DRAFT WATER BOILER — SERIES 3 —

Boiler Manual