SERVICE TECHNICIAN ONLY — read and follow completely.

High temperature limit

• To comply with ASME, UL 726 or Canadian requirements, an additional

high temperature limit is needed.

• Install the secondary control in the supply piping between boiler and

isolation valve.

• Set the control to a minimum of 20˚F above the set point of the com-

bination control.

• The maximum allowable set point is 220˚F.
• Wire the control as shown on page 24.

Limit control

wiring harness

Circulator

wiring

harness

(not

furnished

on “A”

boilers)

Service

switch

on

boiler

Burner

wiring

harness

Burner

disconnect plug

Figure 16

Boiler wiring for forced hot water

Junction box (furnished)

• Junction box houses electrical connections for all

boiler components.

• “P” boilers have harnesses furnished.
• “A” boilers are furnished with burner and limit

harnesses.

• All field-provided high voltage wiring must be

sheathed in flexible metal conduit.

• Connect incoming line voltage “HOT” wire to

service switch, and neutral wire to white wire.

Field-install equipment ground wire to green wire

with wire nut.

• Service switch (15 amp) is provided with boiler. “A”

boilers — install switch as shown.

• Some local codes may require an emergency shut-

off switch installed at a location away from boiler.

Follow local codes.

Burner wiring

• Burner harness incorporates a disconnect plug,

providing a convenient way to disconnect wiring

when burner mounting door is opened.

• All “P” boilers have a power disconnect plug in-

stalled on burner.

• On “A” boilers, mount the plug (provided in water

trim carton) on the burner housing as shown in

Figure 16. For Carlin burners, screw burner plug

into threaded conduit coupling, then mount this

assembly to the burner housing using the chase

nipple. Route wires through housing and make

connections in burner junction box as shown in

boiler wiring diagram.