SERVICE TECHNICIAN ONLY — read and follow completely.

Figure 6

Water boiler controls

Install burner

(also refer to instructions packed with
burner)

Use only burners specified for use on

Weil-McLain GOLD oil boilers. DO

NOT use burners specified for use on

Weil-McLain Model 68 boilers. Contact

individual burner manufacturers for

proper burner selections.

Relief

valve

Water

pressure-temperature

gauge

Limit control / low water cut-off

Drain valve

Circulator

For P-WGO and A-WGO boiler:

1. Secure universal mounting flange and gasket to burner mounting door.

Use three bolts provided.

2. Secure burner on flange with three bolts.

3. Position burner so end of air tube is level to 1½° tilt downward. Open

door to verify burner position. End of air tube should be flush to ¼"

recessed from inside wall of burner door refractory. Check for secure

placement of insulation on target wall, chamber floor and burner

mounting door. Securely close door with nut.

Install burner — all boilers

Part number 550-141-826/1211

15

GOLD

WGO

OIL-FIRED NATURAL DRAFT WATER BOILER — SERIES 3 —