8.3.7 Changing the Power Supply to Maintenance Bypass

This UPS must be completely shut down when performing maintenance and inspections. In
such cases, the power supply to the load will go through the maintenance bypass. Table 8.8
shows the procedure used to change the power supply to this maintenance bypass. Table 8.9
shows how to change the power supply from the maintenance bypass back to the UPS.

Table 8.8 Changing From UPS to maintenance Bypass Power Supply

Step Procedure

LCD/LED

Status (After Execution)

1-3

Same as steps 1-5 in Section 8.3.4 "Stop."

4 Turn

ON

maintenance

bypass AC circuit
breaker 52M. *

,

**

5 Perform

steps

6

through 11 in Table 8.4
“Complete Shutdown”
on page 34 to shut
down the UPS
completely.

→Change to

maintenance bypass
power supply
complete.

When the UPS is shutdown completely, nothing at all will be
displayed on the LCD screen and all LEDs will be unlit.

*

During load operation, always operate the circuit breakers in the following order :

52M ON

→52lL OFF→ 52C OFF

** When power is supplied to the UPS, circuit breaker 52M cannot be turned on.