8.3 Procedures

8.3.1 Startup

Table 8.1 shows the procedure used to start up the UPS.

LED status

: Unlit

: Lit

: Blinking

Table 8.1 Startup Procedures

Step Procedure

LCD/LED

Status (After Execution)

1

Turn on the control
power supply switch
(8A) on the panel.

2

Turn on the bypass AC
input 52C and the AC
output 52L circuit
breakers.

(The UPS will change
to bypass power
supply status and AC
output voltage will be
generated.)

3

Turn on the precharge
circuit switch (6CH)*.

*

The control power supply switch 8A is left in the on state (Do not turn this switch off.)

BYPASS

MOVE #6CH TO ‘ON’ POSITION

BYPASS

WAIT FOR A WHILE

OPERATION GUIDANCE

MOVE #52C AND #52L TO ‘ON’ POSITION

The "BYPASS" LED lit.

BATTERIES

AC

SWITCH

UPS

BYPASS

DISCHARGE

FLOAT CHARGE

EQUAL CHARGE

AC INPUT

CONVERTER

INVERTER

AC OUTPUT

BYPASS INPUT

The "BYPASS INPUT" and The "OUTPUT"LEDs lit.

BATTERIES

AC

SWITCH

UPS

BYPASS

DISCHARGE

FLOAT CHARGE

EQUAL CHARGE

AC INPUT

CONVERTER

INVERTER

AC OUTPUT

BYPASS INPUT

BATTERIES

AC

SWITCH

UPS

BYPASS

DISCHARGE

FLOAT CHARGE

EQUAL CHARGE

AC INPUT

CONVERTER

INVERTER

AC OUTPUT

BYPASS INPUT