- 35 -

6 F 3 H 1 0 0 1

8.3.4 Complete Shutdown

This section describes the procedure used to turn off the control power source and shut
down the UPS completely (to turn everything up to the control power source off).

Table 8.4 Complete Shutdown

Step Procedure

LCD/LED

Status (After Execution)

1-4

Same as steps 1-4 in Section 8.3.3 "Stop."

5 When

the

message

appears, turn off the
main circuit AC input
circuit breaker (52R).

6

Turn off the AC output
circuit breaker (52L).

7 Turn

off

the

Bypass

input circuit breaker
(52C).

BATTERIES

AC

SWITCH

UPS

BYPASS

DISCHARGE

FLOAT CHARGE

EQUAL CHARGE

AC INPUT

CONVERTER

INVERTER

AC OUTPUT

BYPASS INPUT

BATTERIES

AC

SWITCH

UPS

BYPASS

DISCHARGE

FLOAT CHARGE

EQUAL CHARGE

AC INPUT

CONVERTER

INVERTER

AC OUTPUT

BYPASS INPUT

BATTERIES

AC

SWITCH

UPS

BYPASS

DISCHARGE

FLOAT CHARGE

EQUAL CHARGE

AC INPUT

CONVERTER

INVERTER

AC OUTPUT

BYPASS INPUT

The "AC INPUT" LED unlit.

The "AC INPUT" LED unlit.

The "BYPASS INPUT" LED unlit.

BYPASS

MOVE #52C AND #52L TO ‘ON’ POSITION

OPERATION GUIDANCE

MOVE #52C TO ‘OFF’ POSITION

OPERATION GUIDANCE

MOVE #6CH TO ‘OFF’ POSITION

WAIT ABOUT 20 MINUTES

MOVE #8A TO ‘OFF’ POSITION