Toshiba TOSNIC-7000S User Manual

Page 10

background image

- 9 -

6 F 3 H 1 0 0 1

3.

Handling Precautions (continued)

When the unit has stopped due to failure, be sure to remove the memory card
before resetting the LCD Failure Error screen on the panel.

Resetting (restarting) the UPS without removing the memory card will
delete the data needed to determine the cause of the failure.

Do not leave the unit for long periods of time (1 week) with control power source
switch (8A) in the OFF position.

This can cause the backup capacitor on the control board to become
discharged and result in incorrect time display and other problems.