Creating Routing Tables

Section 3-8

explanation of how to create an I/O table using a CX-Programmer, refer to the
CX-Programmer User’s Manual.

Use the following procedure to create the I/O table.

Note With the CJ Series, it is necessary to create an I/O table only when I/O alloca-

tion is performed by the user. With the CS Series, it is always necessary to
create an I/O table.

3-8

Creating Routing Tables

When the FINS communications service is used, routing tables must be cre-
ated in advance. Routing tables are required in the following circumstances.

• When the FINS communications service is used on an Ethernet network

(including when communications are only carried out between FA net-
works via an Ethernet network).

• When there are multiple Communications Units mounted to the PC, and

socket services are requested by executing the CMND(490) instruction.

If neither of these circumstances apply, then a routing table is not required. In
that case, proceed to 3-9 System Setup.

The routing table is required not only for nodes communicating via the FINS
communications service but for all relay nodes on the network.

3-8-1

Routing Table Overview

The routing tables describe the transmission path for FINS messages when
the FINS communications are used. It consists of two tables: A local network
table and a relay network table.

Initial screen

Password

or

(Save or clear the CPU Bus Unit System Setup.)

SHIFT

WRITE

CHG

CH

*DM

000000 I/O TBL ?

000000 I/O TBL

WRIT ????

000000CPU BU ST?

0:CLR 1:KEEP

000000 I/O TBL

WRIT OK