249

Command/Response Reference

Section 11-3

11-3-27 IP ADDRESS READ

Reads the local IP address and subnet mask in the CPU Bus Unit System
Setup and the FINS node number. The values read with this command, how-
ever, are not necessarily the settings actually used for operation. The settings
that are actually used for operation can be confirmed using CONTROLLER
DATA READ (page 218) and ADDRESS INFORMATION READ (page 248).

This command is supported for CJ-series Ethernet Units only.

Command Block

Response Block

Parameters

Number of Addresses (Response)

The number of sets of FINS node numbers, IP addresses, and subnet masks
being returned. The Ethernet Unit is always 0001 (1 decimal).

FINS Node Number (Response)

Node number set on the Ethernet Unit (hexadecimal).

IP Address

The local IP address set in the CPU Bus Unit System Setup for the Ethernet
Unit is returned in order starting from the leftmost bytes in hexadecimal. If the
local IP address set in the allocated words in the DM Area is enabled, 0.0.0.0
is returned.

Subnet Mask (Response)

The subnet mask set in the CPU Bus Unit System Setup for the Ethernet Unit
is returned in order starting from the leftmost bytes in hexadecimal.

Response Codes

67

27

Command
code

67

27

Command
code

Response
code

Number of
addresses

FINS
node
number

IP address

Subnet mask

00

Response code

Description

0000

Normal

1001

Command too large