121
Using Socket Services with Socket Service Request Switches
Section 6-2
Note These response codes will be returned only on large, multilevel networks.
TCP Socket Receive Request
Note These response codes will be returned only on large, multilevel networks.
TCP Socket Send Request
0053
Communications error with remote node (ETIMEDOUT).
No remote node.
0081
The specified socket was closed during open processing.
Response
code
Meaning
0000
Normal end
0302
CPU Unit error; cannot execute.
1100
Number of receive bytes not in allowable range.
1101
The area designation of the Send/Receive Data Address is not in
allowable range.
1103
The bit number in the Send/Receive Data Address is not 00.
110C
Request Switch turned ON during other processing.
2210
The specified socket is not open.
220F
Specified socket is already processing a receive request.
2210
Specified socket has not been connected.
2211
Unit is busy; cannot execute.
2607
Specified Socket Service Parameter Area is already being used for
another socket.
003E
Internal buffer cannot be obtained due to high reception traffic
(ENOBUFS).
0042
(See note.)
ICMP data received (EMSGSIZE).
0044
(See note.)
ICMP data received (ENOPROTOOPT).
0045
(See note.)
Error in communications with remote node (ECONNABORTED).
004B
Error in communications with remote node (ECONNRESET).
004E
(See note.)
ICMP data received (ENETUNREACH).
004F
(See note.)
ICMP data received (EHOSTDOWN).
0051
(See note.)
ICMP data received (EHOSTUNREACH).
0053
Error in communications with remote host (ETIMEDOUT).
0066
Internal memory cannot be obtained; cannot execute.
0080
Receive request timed out.
0081
The specified socket was closed during receive processing.
Response
code
Meaning
0000
Normal end
0302
CPU Unit error; cannot execute.
1100
Number of bytes to send not in allowable range.
1101
The area designation of the Send/Receive Data Address is not in
allowable range.
1103
The bit number in the Send/Receive Data Address is not 00.
Response
code
Meaning