Using Socket Services with CMND(490)

Service request commands can be sent to the Ethernet Unit by executing the
CMND(490) instruction in the ladder diagram. CS/CJ Ethernet Units support
the same functionality as the CV-series Ethernet Unit, so heritage programs
can be easily corrected and reused.

Up to 16 sockets can be connected using CMND(490): 8 UDP sockets and
8 TCP sockets.

The socket service request commands that can be used are listed in the fol-
lowing table. Refer to Section 11 FINS Commands Addressed to Ethernet
Units
f
or details on these commands.

Requests sent to the Ethernet Unit by sending commands through execution
of CMND(40), and when the Unit receives a command, it will return a
response. The response does not, however, indicate that processing has
been completed, and the status of the flags in the Socket Status Words allo-
cated to the Unit must be used to determine when processing has been com-
pleted.

The results of processing will be stored in the words specified when
CMND(490) was executed once the requested processing has been com-
pleted.

Basic FINS Command
Format

The basic format for FINS commands used for socket services is shown in the
following diagram.

Command Code:

Specifies the process code requested from the socket.

Socket Number

Specifies the socket number for the process, between 1 and 8.

Results Storage Area

Specifies the area to store the results of the requested process.

Parameters

Specifies the parameters defined for the command code.

Command code

Name

MRC

SRC

27

01

UDP OPEN REQUEST

02

UDP RECEIVE REQUEST

03

UDP SEND REQUEST

04

UDP CLOSE REQUEST

10

TCP PASSIVE OPEN REQUEST

11

TCP ACTIVE OPEN REQUEST

12

TCP RECEIVE REQUEST

13

TCP SEND REQUEST

14

TCP CLOSE REQUEST

Socket
number

0

1

2

3

4

5

6

7

8

9

10

11

12

Command
code

Results storage area

Parameters

Byte order from
the beginning of
the frame

This manual is related to the following products: