Ab c – Powerware 9335 User Manual

Page 80

background image

Table A. INPUT/OUTPUT Ratings & External Wiring Requirements for

Powerware 9335 – 80 kVA

Ratings

Units

Rating 50/60 Hz

kVA

W

80

Basic unit ratings at
0.8 lagging PF load

INPUT/ OUTPUT

VOLTAGE

480

Amps*

105

AC

INPUT

AC Input to UPS Rectifier (0.95 min. PF)
3 phase, 1 neutral, 1 ground
Minimum conductor size *Max. amps
include full load current plus
battery recharge current

AWG or kcmil (ea)

1/0

AC Input to UPS Bypass - Full Load
Current 3 phase, 1 neutral, 1 ground

Amps*

97

AC

INPUT

Minimum conductor size

AWG or kcmil (ea)

1/0

DC Input from Ext. Battery source to
UPS
(1) positive, (1) negative, (1) mid-point

VDC (nominal)

Amps*

+240 0 -240

167

DC

INPUT

Minimum conductor size

AWG or kcmil (ea)

4/0

AC Output to Critical Load

- Full Load

Current 3 phase, 1 neutral, 1 ground

Amps*

97

AC

OUTPUT

Minimum conductor size

AWG or kcmil (ea)

1/0

A

B

C

*

Full

load,

nominal

voltage

D

Note: Refer to Figure A – 3 on system one line diagram for the bold letter callout
locations.

Read and understand the following notes while planning your installation:

1. Refer to national and local electrical codes for acceptable external wiring practices.

2. Material and labor for external wiring requirements are to be provided by designated

personnel.

3. For external wiring, use 90

o

C copper wire. See the appropriate column in Tables A

and B. When wiring to an external battery cabinet, either 75

o

C or 90

o

C wiring may

be used.


4. Wire ampacities are chosen from Table 310-16 of the NEC.

5. A neutral feeder is required for both the main and bypass inputs to this system.

6. Refer to section 1 of this manual for installation instructions.

A-2

Powerware 9335 (80 kVA and 120 kVA) Installation and Operation

164201396 REV A 07/11/2003