9 set-up service – Powerware 9335 User Manual
Page 57

Powerware 9335 (80 kVA and120 kVA) Installation and Operation
7-9
164201396 REV. A 071103
7.3.9 Set-Up Service
DESCRIPTION LCD
DISPLAY
• This menu is reserved for authorized
service engineers. It is not to be
accessed by End-Users.
• Type in password.
NOTE: Apart from the adjustment of voltages, frequencies, currents, power and battery
run time in the SET-UP Service menu, it is also possible to set and check the
following parameters:
•
UPS Rated Power
•
Module configuration S or future alternate module configurations
•
Single (standard) or Dual Input feed
•
F-converter, 50/60Hz or 60/50Hz
•
Sync window (2-4%)
SET-UP SERVICE
PASSWORD