Pull cable – Polycom SpectraLink SCM408 User Manual
Page 18
SpectraLink 6100 MCU: Installation and Operation: SpectraLink 6000 System
PN: 1725-36097-001_L.doc
18
Determine the amount of wire needed to connect the Base Station to
the MCU by scaling from a floor plan or a sketch, pacing, measuring,
or estimating. Remember to include enough wire to reach the ceiling.
The wire length between the MCU and each Base Station may not
exceed 2,200 cable feet.
Install an extra 25 feet of wire at the Base Station to allow for
possible relocation.
Pull Cable
Pull the cable from the MCU location (usually in the telephone
equipment room) to the Base Station locations designated on the floor
plans.
If the cabling between the MCU and the telephone system or to the
Base Station leaves the building, consult the telephone system
manual, the National Electric Code (NEC), and local codes for
instructions on providing lightning and other over-current protection.
Run all cable before attaching the RJ-45 connectors to the Base
Stations. Label both the demarcation block end and the Base Station
end of each wire with the Base Station number using a wire tie marker
or other form of marker.
Remove bridge taps, multiples, or “Y” connections to the Base
Station wires; these will cause data transmission errors.
The area above some suspended ceilings is used as an
environmental air plenum. The NEC requires that wire installed in
plenums be rated for plenum installation.
- SpectraLink SCE408 SpectraLink SCT416 SpectraLink 1725-36097-001 SpectraLink SCA516 SpectraLink SCK416 SpectraLink SCA408 SpectraLink SCJ408 SpectraLink SCI416 SpectraLink SCN416 SpectraLink SCO416 SpectraLink SCJ416 SpectraLink SCO408 SpectraLink SCS416 SpectraLink SCI408 SpectraLink RCC400 SpectraLink SCK408 SpectraLink SCL408 SpectraLink RCU201 SpectraLink SCA416 SpectraLink SCL416 SpectraLink MOG400 SpectraLink SCM416 SpectraLink SCC408 SpectraLink SCC416 SpectraLink SCD416 SpectraLink SCF416 SpectraLink SCN408 SpectraLink SCE416 SpectraLink SCF4089 SpectraLink SCX416 SpectraLink SCD408