Responding to System Events

When the UPS system is running in Normal mode, it continually

monitors itself and the incoming utility power. In Battery or Bypass

modes, the UPS may issue alarms to let you know exactly what event caused the

change from Normal mode. System events can be indicated by horns, lights on

the UPS, or both.

Select

Active from the Events menu on the LCD screen to look at the Active

System Events screen. This screen shows any currently active alarms, notices,

or commands.

System Event Horns

The system event horn beeps according to the type of event it is signifying:

When the UPS detects an alarm that requires your attention, the horn beeps at

½-second intervals.

When a notice occurs, the horn beeps at 2-second intervals.

If the battery contactor is open and the Bypass mode is unavailable, the horn

beeps every 4 seconds.

System Event Lights

The status indicators on the UPS Monitor Panel work in conjunction with the event

horn to let you know when the UPS is operating in any mode other than Normal.

Only the Normal indicator is visible during normal UPS operation. The others light

to indicate alarms or events. When an alarm occurs, you should first check these

indicators to see what type of event has taken place. For descriptions of the status

indicators, see “Reading the Status Indicators” section of Chapter 9, “Using the

Monitor Panel”.