To Cold Start the UPS from Battery (No AC Input Power):

To start the UPS system when commercial power is not available, perform the

following procedure:

1.

Ensure the feeder breaker is open (no input or bypass power available).

2.

Place the

BATTERY switch in the NORMAL position.

3.

Place the

MODE switch in the NORMAL position.

4.

Ensure the Emergency Power Off

PUSH TO RESET pushbutton is pressed in.

5.

Close input breaker

CB1.

6.

Place Power Switch S1 (located in the environmental cabinet) to the ON

position.

Logic power comes on for all PCBs and

Horn sounds every 2 seconds.

7.

The following UPS messages are displayed on the Monitor Panel LCD screen:

Status:

Load Off

Alarm:

Converter Offline

Notice:

Bypass AC Under Voltage

Output AC Under Voltage

Converter in Shutdown

8.

Monitor the LCD meter screen for battery voltage.

9.

Press and hold Cold Start switch S2.

The converter K1 contactor closes after 5 seconds.

LCD meter screen should indicate 120 to 130 VDC.

The following message appears on the screen:

Notice:

OK to Close CB2

Converter In Startup

10.

Close battery breaker

CB2.

11.

When the DC reaches 250 VDC, the converter starts.

The DC walks up to 540 VDC.

The inverter starts.

K3 closes.

All fans and blowers are functional.