Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation

164291261 Rev. F 111503

Supervisory Contact Module

An optional Supervisory Contact Module (SCM) establishes an interface between

the UPS manufacturer’s equipment and the customer’s monitor. This interface

allows the customer to monitor operational status of the UPS equipment. A

maximum of two monitoring accessories (RMPs, RIMs, or SCMs) can be installed.

See Table 1 for the number of accessories permitted. Figure 39 shows the SCM,

input connections on TB1, and output connections on TB2.

TB2

Figure 39. Supervisory Contact Module

The SCM provides signals for the following indications:

SYSTEM NORMAL

TB2---1 through TB2---3

NO REDUNDANCY

TB2---4 through TB2---6

ON GENERATOR

TB2---7 through TB2---9

BYPASS NOT AVAILABLE TB2---10 through TB2---12

ON BATTERY

TB2---13 through TB2---15

UPS ALARM

TB2---16 through TB2---18

ON BYPASS

TB2---19 through TB2---21

SHUTDOWN IMMINENT

TB2---22 through TB2---24

See Chapter 6, “Installing a Supervisory Contact Module” for TB2 contact

configurations.