Powerware 5075 kVA User Manual
Page 138
DESCRIPTION:
DATE:
DRAWING NO:
5 of 11
INSTALLATION NOTES
SHEET:
REVISION: B
011500
164201261---1
A---6
Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation
164291261 Rev. F 111503
Table E. External Power Cable Terminations
Terminal Function Voltage
Terminal
Function
Size of Pressure
Termination
Tightening
Torque
N---M (lb---in )
Int Hex
Size
(In.)
AC Input to
UPS (CB1)
E33
Phase ‘A’
2 --- 3/0---250 kcmil
42.4 (375)
3/8
UPS (CB1)
208
E34
Phase ‘B’
2 --- 3/0---250 kcmil
42.4 (375)
3/8
E35
Phase ‘C’
2 --- 3/0---250 kcmil
42.4 (375)
3/8
480
E33
Phase ‘A’
1 --- #4---300 kcmil
42.4 (375)
3/8
480
600
E34
Phase ‘B’
1 --- #4---300 kcmil
42.4 (375)
3/8
600
E35
Phase ‘C’
1 --- #4---300 kcmil
42.4 (375)
3/8
AC Input to
B pass
208
E19
Phase ‘A’
1 --- #4---300 kcmil
42.4 (375)
3/8
Bypass
208
480
600
E20
Phase ‘B’
1 --- #4---300 kcmil
42.4 (375)
3/8
600
E21
Phase ‘C’
1 --- #4---300 kcmil
42.4 (375)
3/8
AC Output to
C itical Load
E25
Phase ‘A’
1 --- #4---300 kcmil
42.4 (375)
3/8
Critical Load
208
480
E26
Phase ‘B’
1 --- #4---300 kcmil
42.4 (375)
3/8
480
600
E27
Phase ‘C’
1 --- #4---300 kcmil
42.4 (375)
3/8
600
E12
Neutral/Gnd. 2 --- #4---500 kcmil
31.1 (275)
3/8
DC Input from
Batte
120
E31
Battery (+)
3 --- 2/0---400 kcmil
42.4 (375)
3/8
Battery
120
E32
Battery (---)
3 --- 2/0---400 kcmil
42.4 (375)
3/8
Customer
Ground
N/A
Ground Ground
2 --- #6---350 kcmil
31.1 (275)
3/8
11.
The UPS and the Environmental cabinets are normally crated separately for shipping and
are bolted together on site.
12.
Do not tilt cabinets more than 10˚ during handling.
13.
Dimensions are in millimeters (inches).
14.
Table F lists the ventilation requirements for full load operation:
Table F.
Air Conditioning or Ventilation
Requirements During Full Load Operation
Ratings
Heat Rejection
BTU/hr (Kg---cal/hr)
50--- 75 KVA
23,000 (5796)
15.
Recommended minimum clearance over the UPS module is 304.8 mm (12 in.).
Required for cooling air exhaust: approximately 614.0 liters/sec (1300 cfm).