Powerware 5075 kVA User Manual
Page 137
DESCRIPTION:
DATE:
DRAWING NO:
4 of 11
INSTALLATION NOTES
SHEET:
REVISION: B
011500
164201261---1
A---5
Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operatio
n
164201261 Rev. F 111503
10.
Refer to Table D for internal power cable terminations and Table E for external power cable
terminations. Drawing 164201014---4 shows the location of these power cable terminals
inside the UPS cabinets. Terminals E9 through E15, and E19 through E35 are UL and CSA
rated at 90˚C. A hex key tool is required to attach wires to terminals.
Table D. Internal Power Cable Terminations
Terminal Function
Terminal
Cable
Number
Function
Size of
Termination
Tightening
Torque
N---M
(lb---in )
Bolt or
Hex
Size
(In.)
AC Input to UPS
Rectifie f o
E1
250
Phase ‘A’
1 --- 1 bolt mounting
9.0 (78)
1/4 bolt
Rectifier from
Environmental
E2
251
Phase ‘B’
1 --- 1 bolt mounting
9.0 (78)
1/4 bolt
Environmental
Cabinet
E3
252
Phase ‘C’
1 --- 1 bolt mounting
9.0 (78)
1/4 bolt
AC Input to Bypass
T a sfo e f o
E13
227
Phase ‘A’
1 --- #4---500 kcmil
42.4 (375)
3/8
Transformer from
Environmental
E14
228
Phase ‘B’
1 --- #4---500 kcmil
42.4 (375)
3/8
Environmental
Cabinet
E15
229
Phase ‘C’
1 --- #4---500 kcmil
42.4 (375)
3/8
AC Output to
E i o
e tal
E9
237
Phase ‘A’
1 --- #6---350 kcmil
31.1 (275)
3/8
Environmental
Cabinet
E10
238
Phase ‘B’
1 --- #6---350 kcmil
31.1 (275)
3/8
Cabinet
E11
239
Phase ‘C’
1 --- #6---350 kcmil
31.1 (275)
3/8
E12
600
Neutral/
Gnd.
2 --- #4---500 kcmil
31.1 (275)
3/8
DC Input from
Environmental
E4
205
Battery (+)
1 --- 1 bolt mounting
32 (277)
3/8 bolt
Environmental
Cabinet
E5
206
Battery (---)
1 --- 1 bolt mounting
32 (277)
3/8 bolt