INSTALLATION NOTES

SHEET:

REVISION: B

011500

164201261---1

A---5

Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operatio

n

164201261 Rev. F 111503

10.

Refer to Table D for internal power cable terminations and Table E for external power cable

terminations. Drawing 164201014---4 shows the location of these power cable terminals

inside the UPS cabinets. Terminals E9 through E15, and E19 through E35 are UL and CSA

rated at 90˚C. A hex key tool is required to attach wires to terminals.

Table D. Internal Power Cable Terminations

Terminal Function

Terminal

Cable

Number

Function

Size of

Termination

Tightening

Torque

N---M

(lb---in )

Bolt or

Hex

Size

(In.)

AC Input to UPS

Rectifie f o

E1

250

Phase ‘A’

1 --- 1 bolt mounting

9.0 (78)

1/4 bolt

Rectifier from

Environmental

E2

251

Phase ‘B’

1 --- 1 bolt mounting

9.0 (78)

1/4 bolt

Environmental

Cabinet

E3

252

Phase ‘C’

1 --- 1 bolt mounting

9.0 (78)

1/4 bolt

AC Input to Bypass

T a sfo e f o

E13

227

Phase ‘A’

1 --- #4---500 kcmil

42.4 (375)

3/8

Transformer from

Environmental

E14

228

Phase ‘B’

1 --- #4---500 kcmil

42.4 (375)

3/8

Environmental

Cabinet

E15

229

Phase ‘C’

1 --- #4---500 kcmil

42.4 (375)

3/8

AC Output to

E i o

e tal

E9

237

Phase ‘A’

1 --- #6---350 kcmil

31.1 (275)

3/8

Environmental

Cabinet

E10

238

Phase ‘B’

1 --- #6---350 kcmil

31.1 (275)

3/8

Cabinet

E11

239

Phase ‘C’

1 --- #6---350 kcmil

31.1 (275)

3/8

E12

600

Neutral/

Gnd.

2 --- #4---500 kcmil

31.1 (275)

3/8

DC Input from

Environmental

E4

205

Battery (+)

1 --- 1 bolt mounting

32 (277)

3/8 bolt

Environmental

Cabinet

E5

206

Battery (---)

1 --- 1 bolt mounting

32 (277)

3/8 bolt