Battery Test Printout (Ctrl + B)
This key sequence prints the Battery Test Log. The log consists of a history of the
last 30 battery tests that were run and the results of those tests. The most recent
test will appear at the bottom of the log. Figure 46 shows a sample of the Battery
Test Log.
Uninterruptible Power System
UPS System Normal
Alarm:
None
Notice:
None
12 APR 95 15:39:31
UPS # 1
AUG 14 23:45 498.0 1.00
0000
SEP
11 23:45 498.0 1.00
0000
OCT
9 23:45 498.0 1.00
0000
NOV 13 23:45 498.0 0.99
0000
DEC 11 23:45 498.0 0.99
0000
JAN
8 23:45 498.0 0.98
0000
FEB
12 23:45 498.0 0.98
0000
MAR 12 23:41 000.0 0.00
0003
APR
9 23:45 496.2 0.98
0000
Battery Test Log
Date/Time
Volts Health
Data
Figure 46. Battery Test Log
The
Date/Time field is the date and time of the battery test.
The
Volts field is a measured value of the battery voltage during the test. This field
will display 000.0 if the test did not run to completion.
The
Health field is a relative measurement of your batteries condition. This number
can be used to chart the condition of your batteries. If a sudden change of this
number occurs relative to the previous test results, it is an indication that your
batteries may need attention. This display is 0.00 if the test does not run to
completion.
The
Data field is a value to be used by your field service engineer to gain more
information about the battery tests.
If the battery test does not complete, the Volts and Health field will read zero and
the UPS Event History Log will report either Battery Test Failed, Battery Test
Aborted (Load), or Battery Test Aborted (Utility). If the test ran to completion,
Battery Passed Test will appear in the UPS Event History Log.