Battery Test Printout (Ctrl + B)

This key sequence prints the Battery Test Log. The log consists of a history of the

last 30 battery tests that were run and the results of those tests. The most recent

test will appear at the bottom of the log. Figure 46 shows a sample of the Battery

Test Log.

Uninterruptible Power System

UPS System Normal

Alarm:

None

Notice:

None

12 APR 95 15:39:31

UPS # 1

AUG 14 23:45 498.0 1.00

0000

SEP

11 23:45 498.0 1.00

0000

OCT

9 23:45 498.0 1.00

0000

NOV 13 23:45 498.0 0.99

0000

DEC 11 23:45 498.0 0.99

0000

JAN

8 23:45 498.0 0.98

0000

FEB

12 23:45 498.0 0.98

0000

MAR 12 23:41 000.0 0.00

0003

APR

9 23:45 496.2 0.98

0000

Battery Test Log

Date/Time

Volts Health

Data

Figure 46. Battery Test Log

The

Date/Time field is the date and time of the battery test.

The

Volts field is a measured value of the battery voltage during the test. This field

will display 000.0 if the test did not run to completion.
The

Health field is a relative measurement of your batteries condition. This number

can be used to chart the condition of your batteries. If a sudden change of this

number occurs relative to the previous test results, it is an indication that your

batteries may need attention. This display is 0.00 if the test does not run to

completion.
The

Data field is a value to be used by your field service engineer to gain more

information about the battery tests.
If the battery test does not complete, the Volts and Health field will read zero and

the UPS Event History Log will report either Battery Test Failed, Battery Test

Aborted (Load), or Battery Test Aborted (Utility). If the test ran to completion,

Battery Passed Test will appear in the UPS Event History Log.