DESCRIPTION:

DATE:

DRAWING NO:

6 of 11

INSTALLATION NOTES

SHEET:

REVISION: E

093001

164201261---1

A---7

Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operatio

n

164201261 Rev. F 111503

16.

Battery voltage is computed at 2 volts per cell as defined by Article 480 of the NEC. Rated

battery current is computed at 1.8 volts per cell.

17.

The battery wiring used between the battery and the UPS should not allow a voltage drop

of more than 1% of nominal DC voltage at rated battery current.

18.

A battery disconnect switch is recommended, and may be required by NEC or local codes

when batteries are remotely located. The battery disconnect switch may be supplied as an

accessory, and should be installed between the battery and the UPS.

19.

Table G lists the maximum rating for input circuit protective devices (circuit breakers).

Table G. Maximum Input Circuit Breaker Ratings

Balanced Power System

Input Voltage Rating

Balanced Power System

208V

400V

480V

600V

Balanced Power 75

400

N/A

175

150

Balanced Power 62.5

350

175

150

125

Balanced Power 50

300

150

125

100

20.

Source protection for AC input should be treated as if supplying a three phase transformer

with a rating 1.4 times the UPS kVA rating, to allow for transformer magnetization inrush

current.

21.

The input breaker (CB1) has a trip rating of 150 amps AT for the 400, 480 and 600 volt input

UPS and 320 amps AT for the 208 volt input UPS.

22.

The bypass feed into this equipment utilizes either three or four wires. The rectifier feed

into this equipment utilizes three wires. However, the phases must be symmetrical about

ground (i.e., from a Wye source) for proper equipment operation. Failure to follow these

instructions will void the product warranty.

23.

The line-to-line unbalanced output capability of the UPS is limited by the full load per phase

current values for AC output to critical load shown in Tables A through C. The

recommended line-to-line load unbalance is 50% or less.

24.

Table H lists the maximum rating for output circuit protection devices (circuit breakers).

Table H. Maximum Output Circuit Breaker Ratings

Balanced Power System

Output Voltage Rating

Balanced Power System

208V

400V

480V

Balanced Power 75

300

N/A

125

Balanced Power 62.5

225

125

100

Balanced Power 50

175

90

80