Using the menu options – Powerware 5075 kVA User Manual
Page 63

55
Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operatio
n
164201261 Rev. F 111503
Using the Menu Options
The UPS
menus allow you to display data in the information area to help you
monitor and control UPS operation. The following menus and options are
available:
•
Meters
Displays UPS performance meters for the system or critical load.
•
Events
Displays the list of Active System Events and a historical log of
system events.
•
Statistics
Displays statistical information about UPS operations for the
battery, load, or line.
•
Graphics
Displays a real-time graphic representation of the flow of current
through the internal UPS components.
•
Setup
Allows you to configure the UPS communications port and set
the date and time for the timestamp.
Figure 25 shows the LCD screen as it appears when you first start the UPS. The Meters
menu is displayed in the menu box, with the System option highlighted. In the
information area, the system meters show their current readings.
Uninterruptible Power System
System Normal
Alarm:
None
Notice: None
Meters
System
Load Amps
Events Statistics Graphics Setup
Input
Output
Bypass
Battery
VAB
480
VBC
VCA
KW
69
KVA
73
IA
IB
IC
FREQ
60.0
PF
0.95
V
540
I
000
Meters
88
480
480
88
88
VAB
480
VBC
VCA
480
480
IA
IB
IC
90
90
90
IN
000
VAB
480
VBC
VCA
480
480
FREQ
60.0
KVA
75
KW
60
PF
0.80
Battery
04 MAY 1998
14:25:45
100%
Percent
Figure 25. System Meters Screen (Typical for Powerware BPIII HE 75 480/480V Unit)
The Input area shows the phase-to-phase voltage, frequency, and phase current of the
incoming utility, followed by the KVA, KW, and power factor measurements. The output
area shows the same information for the power being output by the UPS.
The Bypass area shows the phase-to-phase voltage of the bypass source. The Battery
area displays the DC voltage (V) and the DC current (I) at the inverter side of the DC
to DC voltage converter.