beautypg.com

Using the operating controls – Powerware 5075 kVA User Manual

Page 72

background image

64

Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation

164291261 Rev. F 111503

Using the Operating Controls

Although the operating controls appear easy to use, you should read these

instructions and thoroughly understand how the controls work before attempting

to use them. Refer to oneline drawing 164201261---3 in Appendix A to clarify control

functions. Refer to Chapter 9 --- Using the Monitor Panel for instructions on using

the monitor panel.

CAUTION:

Incorrect use of the power controls can cause a loss of power to your

critical load.

The following paragraphs describe the switches on the Control Panel (see Figure 34).:

The

MODE switch is a two-position rotary switch that controls the manual

transfer of the UPS to and from Bypass mode. The

MODE switch is used to:

--- Place the critical load in Bypass mode when the UPS is operating in Normal

mode and the bypass source is within acceptable limits. If the transfer does

not occur within 2 seconds, an alarm sounds.

--- Prevent transfer to Normal mode when the UPS is in Bypass mode.
--- Shut down the

power processing unit (inverter and rectifier) of the UPS.

OFF

MODE

BATTERY

PUSH

TO RESET

NORMAL

BYPASS

NORMAL

START

Figure 34. UPS Control Panel

The

BATTERY switch is a two-position rotary switch that allows you to manually

enable or disable the Battery Breaker CB2. The battery switch is also used to

reset the DC to DC converter if the converter shuts down during normal

operation.

The

PUSH TO RESET pushbutton is described in the “Resetting UPS System

after Emergency Power Off” section of this chapter.