Operating information, A(boiler status bar), B(call for heat indicators) – Lochinvar KNIGHT XL 801 User Manual

Page 69

background image

69

11

Operating information

(continued)

Status Display Screens

Section

Display

Description

A

(Boiler Status

Bar)

STANDBY

The unit has not received a call for heat from a remote thermostat nor
has it received a call for heat from a DHW thermostat.

START

The unit has begun a burn cycle and is checking all safety circuits.

PREPURGE

The unit has initiated a 10 second purge period on a call for heat.

IGNITION

The unit has begun a 4 second spark period to ignite the main burner.

The unit has fi red and is running at the displayed percentage.

POSTPURGE

The call for heat has been satisfi ed and the unit runs the fan for an
additional 10 seconds to clear the combustion chamber and vent
system of residual fl ue products.

SHUTDOWN

The unit has been placed in the OFF position.

The controlled temperature has exceeded its set point and its offset.

BLOCKED

The unit has detected a condition that has temporarily interrupted
the current call for heat.

B

(Call for Heat

Indicators)

Room Thermostat 1 has a call for heat.

Room Thermostat 2 has a call for heat.

Room Thermostat 3 has a call for heat.

The tank thermostat or sensor has a call for heat.

Indicates which room thermostat demand shows priority.

The unit is being controlled by a 0 - 10V BMS signal.

The member unit is supplying heat while in Cascade Mode.

A

C

D

B

F

E

(BOILER

STATUS)

(OPERATIONAL

INFORMATION)

(LEFT SELECT

KEY)

(RIGHT SELECT KEY)

(NAVIGATION DIAL)

(CALL FOR

HEAT)

Figure 11-2 Status Display Screen

%

Installation & Operation Manual