Page 17: Requirements for installation in canada

17
3
General
venting
(continued)
PVC/CPVC vent piping materials
Use only the materials listed in Table 3A 
(pg. 18) for vent pipe, and fi ttings. Failure 
to comply could result in severe personal 
injury, death, or substantial property 
damage.
Installation must comply with local 
requirements and with the National Fuel 
Gas Code, ANSI Z223.1 for U.S. installations 
or CSA B149.1 for Canadian installations.
Install vent and combustion air piping
ƽ DANGER
The Knight XL must be vented and 
supplied with combustion and ventilation 
air as described in this section. Ensure the 
vent and air piping and the combustion 
air supply comply with these instructions 
regarding vent system, air system, and 
combustion air quality. See also Section 1 
of this manual.
Inspect fi
nished vent and air piping
thoroughly to ensure all are airtight and 
comply with the instructions provided and 
with all requirements of applicable codes.
Failure to provide a properly installed vent 
and air system will cause severe personal 
injury or death.
All PVC vent pipes must be glued, properly 
supported, and the exhaust must be pitched 
a minimum of a 1/4 inch per foot back to 
the boiler (to allow drainage of condensate).
This appliance requires a special venting 
system. The vent connection to the appliance 
must be made with the starter CPVC pipe 
section provided with the appliance if PVC/
CPVC vent is to be used. For stainless steel 
venting use an adapter from Table 3B (page 
20) that corresponds with the intended 
vent manufacturer to be used and discard 
the CPVC starter piece. The fi eld provided 
vent fi ttings must be cemented to the CPVC 
pipe section using an “All Purpose Cement” 
suitable for PVC and CPVC pipe. Use only 
the vent materials, primer, and cement 
specifi ed in this manual to make the vent 
connections. Failure to follow this warning 
could result in fi re, personal injury, or 
death.
ƽ WARNING
NOTICE
ƽ WARNING
ƽ WARNING
For closet and alcove installations, CPVC 
or stainless steel material MUST BE used in 
a closet/alcove structure. Failure to follow 
this warning could result in fi re, personal 
injury, or death.
NOTICE
Requirements for installation in 
Canada
1. Installations must be made with a vent pipe system 
 certifi ed to ULC-S636.
IPEX is an approved vent manufacturer in Canada
supplying vent material listed to ULC-S636.
2. The
fi rst three (3) feet of plastic vent pipe from the
appliance
fl ue outlet must be readily accessible for visual
inspection.
3. The components of the certifi ed vent system must not be 
 
interchanged with other vent systems or unlisted
 pipe/fi ttings. For concentric vent installations, the inner 
 
vent tube must be replaced with fi eld supplied certifi ed vent
material to comply with this requirement.
Installing vent or air piping
Improper installation of PVC or CPVC 
systems may result in injury or death.
ƽ CAUTION
Use only cleaners, primers, and solvents that 
are approved for the materials which are 
joined together.
NOTICE
1. Work from the boiler to vent or air termination. Do not 
 
exceed the lengths given in this manual for the air or vent
piping.
2. Cut pipe to the required lengths and deburr the inside and 
 
outside of the pipe ends.
3. Chamfer outside of each pipe end to ensure even cement 
 
distribution when joining.
4. Clean all pipe ends and fi ttings using a clean dry rag.
(Moisture will retard curing and dirt or grease will prevent
adhesion.)
5. Dry
fi t vent or air piping to ensure proper fi t up before
assembling any joint. The pipe should go a third to
two-thirds into the fi tting to ensure proper sealing after
cement is applied.
ƽ WARNING
Insulation should not be used on PVC 
or CPVC venting materials. The use of 
insulation will cause increased vent wall 
temperatures, which could result in vent 
pipe failure.