The Knight XL - How it works...

1. Stainless steel heat exchanger

Allows system water to fl ow through specially designed

coils for maximum heat transfer, while providing protection

against

fl ue gas corrosion. The coils are encased in a jacket that

contains the combustion process.

2. Combustion chamber access cover

Allows access to the combustion side of the heat exchanger

coils.

3. Blower

The blower pulls in air and gas through the venturi (item 5).

Air and gas mix inside the blower and are pushed into the

burner, where they burn inside the combustion chamber.

4. Gas

valve

The gas valve senses the negative pressure created by the

blower, allowing gas to fl ow only if the gas valve is powered and

combustion air is fl owing.

5. Venturi

The venturi controls air and gas fl ow into the burner.

6. Flue gas sensor (limit rated)

This sensor monitors the fl ue gas exit temperature. The

control module will modulate and shut down the boiler if the

fl ue gas temperature gets too hot. This protects the fl ue pipe from

overheating.

7. Boiler outlet temperature sensor (housed with the

high limit sensor)

This sensor monitors boiler outlet water temperature (system

supply). If selected as the controlling sensor, the control

module adjusts boiler fi ring rate so the outlet temperature is

correct.

8. Boiler

inlet

temperature

sensor

This sensor monitors return water temperature (system

return). If selected as the controlling sensor, the control

module adjusts the boiler fi ring rate so the inlet temperature is

correct.

9. Temperature and pressure gauge (fi eld installed, not

shown)

Monitors the outlet temperature of the boiler as well as the

system water pressure.

10. Electronic LCD display

The electronic display consists of 4 buttons, a navigation dial

and a multiple line liquid crystal display.

11. Flue pipe adapter

Allows for the connection of the PVC vent pipe system to the

boiler.

12. Burner (not shown)

Made with metal fi ber and stainless steel construction, the

burner uses pre-mixed air and gas and provides a wide range of

fi ring rates.

13. Water outlet (system supply)

A 1-1/2" or 2" NPT (depending on the model) water

connection that supplies hot water to the system.

14. Water inlet (system return)

A 1-1/2" or 2" NPT (depending on the model) water connection

that returns water from the system to the heat exchanger.

15. Gas connection pipe

Threaded pipe connection of 1". This pipe should be connected

to the incoming gas supply for the purpose of delivering gas to

the

boiler.

16. SMART SYSTEM Control Module

The SMART SYSTEM Control responds to internal and

external signals and controls the blower, gas valve, and pumps

to meet the heating demand.

17. Manual air vent

Designed to remove trapped air from the heat exchanger

coils.

18. Air intake adapter

Allows for the connection of the PVC air intake pipe to the

boiler.

19. High voltage junction box

The junction box contains the connection points for the line

voltage power and all pumps.

20. Boiler drain port

Location from which the heat exchanger can be drained.

21. Low voltage connection board

The connection board is used to connect external low voltage

devices.

22. Low voltage wiring connections (knockouts)

Conduit connection points for the low voltage connection

board.

23. Condensate drain connection

Connects the condensate drain line to a 1/2" PVC union.

24. Access cover - front

Provides access to the gas train and the heat exchanger.

25. Ignition electrode

Provides direct spark for igniting the burner.

26. Flame inspection window

The quartz glass window provides a view of the burner surface

and

fl ame.

27. Gas shutoff valve

Manual valve used to isolate the gas valve from the gas supply.

28. Relief valve

Protects the heat exchanger from an over pressure condition.

The relief valve provided with the unit is set at 50 PSI.

29. Flame sensor

Used by the control module to detect the presence of burner

fl ame.

30. Line voltage wiring connections (knockouts)

Conduit connection points for the high voltage junction box.

31. Top panel

Removable panel to gain access to the internal components.

32. Power switch

Turns 120 VAC ON/OFF to the boiler.

33. Leveling legs

Used to allow the heat exchanger to be leveled. This is needed

for the proper draining of the condensate from the combustion

chamber.

34.

Air shroud (Model 501 only)

The air shroud controls air and gas fl ow into the burner.

35. Air pressure switch

The air pressure switch detects blocked fl ue/inlet conditions.

break the control circuit, shutting the boiler down.

36. Pump relay board

The pump relay board is used to connect the boiler, system and

DHW

pumps.

37.

Transformer

The transformer provides 24V power to the integrated control.

38.

High limit sensor (housed with the outlet temperature

sensor)

Device that monitors the outlet water temperature. If the

temperature

exceeds its setting, the integrated control will break

the control circuit, shutting the boiler down.

39.

Over-temp switch (located underneath access cover)

Used to detect excessive temperatures on the upper coil of the

heat

exchanger.

Installation & Operation Manual