beautypg.com

Sidewall direct venting, Vent/air termination – sidewall, Prepare wall penetrations – Lochinvar KNIGHT XL 801 User Manual

Page 25: Installation & operation manual

background image

25

12” (305 MM)

MIN

BIRD

SCREEN

(TYPICAL)

12” (305 MM)

MIN

12” (305 MM)

MIN

Figure 4-3B Alternate Clearance to Gravity Air Inlets
w/Field Supplied Fittings

36” (914 MM)

MIN

7’ (2.1 M) MIN ABOVE ANY

PUBLIC WALKWAY

IF LESS

THAN 10’ (3 M)

FORCED AIR

INLET

BIRD

SCREEN

(TYPICAL)

Figure 4-4B Alternate Clearance to Forced Air Inlets
w/Field Supplied Fittings

4

Sidewall direct venting

(continued)

Vent/air termination – sidewall

FORCED AIR

INLET

VENT / AIR

TERMINATION

7' MIN. ABOVE ANY

PUBLIC WALKWAY

IF LESS

THAN 10’

36"

MIN.

Figure 4-4A Clearance to Forced Air Inlets

VENT PIPING

GALVANIZED

THIMBLE

VENT CAP

AIR PIPING

WALL PLATE

VENT PLATE

Figure 4-5A Sidewall Termination Assembly

Prepare wall penetrations

1. Use the factory supplied wall plate as a template to locate

the vent and air intake holes and mounting holes.

Air pipe penetration:
a. Cut a hole for the air pipe. Size the air pipe hole as

close as desired to the air pipe outside diameter.

Vent pipe penetration:
a. Cut a hole for the vent pipe. For either combustible or

noncombustible construction, size the vent pipe hole

with at least a 1/2 inch clearance around the vent pipe

outer

diameter:

• 5½ inch hole (140 mm) hole for 4 inch (102 mm)

vent pipe

• 7½ inch hole (191 mm) hole for 6 inch (152 mm)
vent pipe

Drill 3/16" diameter holes for inserting the plastic anchors
into the wall.

2. Install the vent and air intake piping through the wall into

the vent plate openings. Seal all gaps between the pipes and

wall. Use RTV silicone sealant to seal the air pipe. Use the

cement/primer listed in Table 3A on page 18 to seal the vent

pipe.

3. Mount and secure the vent plate to the wall using stainless

steel screws. Seal around the plate to the wall assuring no

air

gaps.

4. Assemble the vent cap to the vent plate (see FIG. 4-4A).

Insert the stainless steel screws into the vent cap screw hole

openings and securely attach the vent cap to the vent plate.

5. Seal all wall cavities.

Installation & Operation Manual