Model Kit

Number

Equivalent

Vent Length

400

CVK3007

5 Feet (1.5 m)

501

CVK3007

30 Feet (9 m)

601

CVK3007

30 Feet (9 m)

3

General

venting

(continued)

Vent, air piping and termination:

The Knight XL vent and air piping can be installed through the
roof or through a sidewall. Follow the procedures in this manual
for the method chosen. Refer to the information in this manual
to determine acceptable vent and air piping length.

Removing from existing vent

Follow the instructions in Section 1, page 12 of this manual
when removing a boiler from an existing vent system.

Vent and air piping

Vent and air system:

Installation must comply with local
requirements and with the National Fuel Gas
Code, ANSI Z223.1 for U.S. installations or
CSA B149.1 for Canadian installations.

You must also install air piping from outside to the boiler air
intake adapter. The resultant installation is direct vent (sealed
combustion).

You may use any of the vent/air piping methods covered in this
manual. Do not attempt to install the Knight XL using any
other means.

DO NOT mix components from different
systems. The vent system could fail,
causing leakage of fl ue products into the
living space. Use only approved stainless
steel, PVC or CPVC pipe and fi ttings. For
PVC/CPVC use with primer and cement
specifi cally designed for the material used.

NOTICE

ƽ WARNING

Table 3E Concentric Vent Kit Equivalent Vent Lengths

The appliance output rating will reduce
by up to 1.5% for each 25 feet (68 m) of
vent length.

NOTICE

Minimum / Maximum allowable

combustion air and vent piping lengths

are as follows:

Combustion Air = 12 equivalent feet (3.7 m) minimum /
100 equivalent feet (30.5 m) maximum

Vent = 12 equivalent feet (3.7 m) minimum / 100 equivalent
feet (30.5 m) maximum

When determining equivalent combustion air and vent
length, add 5 feet (1.5m) for each 90° elbow and 3 feet (.9 m)
for each 45° elbow.

EXAMPLE: 20 feet (6 m) of PVC pipe + (3) 90° elbows +
(3) 45° elbows + (1) concentric vent kit (CVK3007) = 49
equivalent feet (15 m) of piping.

Model Air

Intake

Vent

400 - 601

4 inches (102 mm)

4 inches (102 mm)

701 - 801

4 inches (102 mm)

6 inches (152 mm)

The Knight XL uses model specifi c combustion air intake and
vent piping sizes as detailed in Table 3D below.

Table 3D Air Intake/Vent Piping Sizes

Increasing or decreasing combustion air
or vent piping is not authorized.

NOTICE

Optional room air

Commercial applications utilizing the Knight XL boiler may
be installed with a single pipe carrying the fl ue products to the
outside while using combustion air from the equipment room.
In order to use the room air venting option the following
conditions and considerations must be followed.

The unit MUST be installed with the appropriate

room air kit (Table 3F).

• The equipment room MUST be provided with

properly sized openings to assure adequate

combustion air. Please refer to instructions provided

with the room air kit.

There will be a noticeable increase in the noise level

during normal operation from the inlet air opening.

Using the room air kit makes the unit vulnerable to

combustion air contamination from within the

building. Please review Section 1, Prevent

Combustion Air Contamination, to ensure proper

installation.

Vent system and terminations must comply with the

standard venting instructions set forth in this manual.

NOTICE

Optional room air is intended for
commercial applications. Combustion air
piping to the outside is recommended for
residential applications.

Installation & Operation Manual