Hydronic piping – Lochinvar KNIGHT XL 801 User Manual
Page 36

36
6
Hydronic piping
System water piping methods
The Knight XL is designed to function in a closed loop 
pressurized system not less than 12 psi (83 kPa). A temperature 
and pressure gauge is included to monitor system pressure 
and outlet temperature and should be located on the boiler 
outlet.
It is important to note that the boiler has a minimal amount 
of pressure drop which must be fi gured in when sizing 
the circulators. Each boiler installation must have an air 
elimination device, which will remove air from the system. 
Install the boiler so the gas ignition system components 
are protected from water (dripping, spraying, etc.) during 
appliance operation or basic service of circulator replacement, 
valves, and others. 
Observe a minimum of 1/4 inch (6 mm) clearance around all 
un-insulated hot water pipes when openings around the pipes 
are not protected by non-combustible materials. 
Low water cutoff device
On a boiler installed above radiation level, some states and 
local codes require a low water cutoff device at the time of 
installation. 
Chilled water system
If the boiler supplies hot water to heating coils in air handler 
units, fl ow control valves or other devices must be installed to 
prevent gravity circulation of heater water in the coils during 
the cooling cycle. A chilled water medium must be piped in 
parallel with the heater. 
Freeze protection
Freeze protection for new or existing systems must use 
glycol that is specially formulated for this purpose. This 
includes inhibitors, which prevent the glycol from attacking 
the metallic system components. Make certain to check that 
the system fl uid is correct for the glycol concentration and 
inhibitor level. The system should be tested at least once 
a year and as recommended by the producer of the glycol 
solution. Allowance should be made for the expansion of the 
glycol solution in the system piping. 
General piping information
Basic steps are listed below along with illustrations on the 
following pages (FIG.’s 6-7 through 6-11), which will guide you 
through the installation of the Knight XL (reference FIG.’s 6-4A 
and 6-4B).
1. Connect the system return marked “Inlet”.
2. Connect the system supply marked “Outlet”.
3. Install purge and balance valve or shutoff valve and drain
on system return to purge air out of each zone.
4. Install
a
backfl ow preventer on the cold feed make-up water
line.
5. Install a pressure reducing valve on the cold feed make-up
water line, (15 psi (103 kPa) nominal). Check temperature 
and pressure gauge (shipped separately), which should read 
a minimum pressure of 12 psi (83 kPa).
6. Install a circulator as shown on the piping diagrams in this
section. Make sure the circulator is properly sized for the 
system and friction loss.
7. Install an expansion tank on the system supply. Consult the
tank manufacturer’s instruction for specifi c information 
relating to tank installation. Size the expansion tank for the 
required system volume and capacity.
8. Install an air elimination device on the system supply.
9. Install a drain valve at the lowest point of the system.
Note: The boiler cannot be drained completely of water 
without purging the unit with an air pressure of 15 psi 
(103 kPa).
10. This appliance is supplied with a relief valve sized in
accordance with ASME Boiler and Pressure Vessel Code, 
Section IV (“Heating Boilers”). Pipe the discharge of the 
safety relief valve to prevent injury in the event of pressure 
relief. Pipe the discharge to a drain. Provide piping that is 
the same size as the safety relief valve outlet. Never block 
the outlet of the safety relief valve.
11. On any pre-existing system, it is good practice to install
a fi eld supplied strainer to prevent damage to the heat 
exchanger.
See the piping illustrations included in this section, FIG.’s 6-7 
and 6-11 for suggested guidelines in piping the Knight XL.
Please note that these illustrations are 
meant to show system piping concept only, 
the installer is responsible for all equipment 
and detailing required by local codes.
Use only inhibited propylene glycol 
solutions, which are specifi cally formulated 
for hydronic systems. Ethylene glycol is 
toxic and can attack gaskets and seals used 
in hydronic systems.
ƽ WARNING
NOTICE
ƽ WARNING The relief valve, tee and any other necessary
fi ttings are shipped in the install kit with the 
boiler and are to be fi eld installed (FIG.’s 6-1 
and 6-2).
Installation & Operation Manual
