Gas connections, Check inlet gas supply – Lochinvar KNIGHT XL 801 User Manual

Page 48

background image

48

Nominal

Iron Pipe

Size

(inches)

Natural Gas Pipe Capacity Chart

Length of Pipe in Straight Feet

Maximum

Capacity of Pipe
in Thousands of

Btu/hr per hour

for gas pressures

of 14 Inches

Water Column

(0.5 PSIG) or less

and a pressure

drop of 0.5 Inch

Water Column

(Based on NAT
GAS, 1025 Btu/

hr per Cubic Foot

of Gas and 0.60

Specifi c Gravity)

10

20

30

40

50

60

70

80

90

100

125

150

175

200

1/2

175

120

97

82

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

3/4

369

256

205

174

155

141

128

121

113

106

95

86

79

74

1

697

477

384

328

292

267

246

236

210

200

179

164

149

138

1-1/4

1400

974

789

677

595

543

502

472

441

410

369

333

308

287

1-1/2

2150

1500

1210

1020

923

830

769

707

666

636

564

513

472

441

2

4100

2820

2260

1950

1720

1560 1440 1330 1250 1180 1100

974

871

820

2-1/2

6460

4460

3610

3100

2720

2460 2310 2100 2000 1900 1700 1540 1400 1300

3

11200 7900

6400

5400

4870

4410 4000 3800 3540 3330 3000 2720 2500 2340

4

23500 16100 13100 11100 10000 9000 8300 7690 7380 6870 6150 5640 5130 4720

7

Gas connections

Table 7A Natural Gas Pipe Size Chart

The gas piping must be sized for the proper fl ow and length of
pipe, to avoid excessive pressure drop. Both the gas meter and
the gas regulator must be properly sized for the total gas load.

If you experience a pressure drop greater than 1 inch w.c.
(249 Pa), the meter, regulator, or gas line is undersized or in
need of service. Perform the steps below when checking inlet
gas supply:

1. Turn the main power switch to the “OFF” position.

2. Shut off gas supply at the manual gas valve in the gas

piping to the appliance.

3. On Models 400 - 501 loosen the set screw one (1) full turn

from inside the pressure tap on top of the gas valve. On

Models 601 - 801 remove the 1/8" (3 mm) pipe plug on the

inlet

fl ange to the valve and install a suitable 1/8" (3 mm)

fi tting (fi eld supplied) for the manometer tubing. Place

the tubing of the manometer over the tap once the set

screw is loosened or the 1/8" (3 mm) fi tting is installed

(depending on model) as shown in FIG.’s 7-5 thru 7-7 on

page

49.

4. Slowly turn on the gas supply at the fi eld installed

manual gas valve.

5. Turn the power switch to the “ON” position.

6. Adjust the temperature set point on the control panel of

the SMART SYSTEM control module to call for heat.

7. Observe the gas supply pressure as the burner fi res at

100% of rated input. Percent of burner input will be

displayed on the control panel.

8. Ensure inlet pressure is within specifi ed range.

Minimum and maximum gas supply pressures are

specifi ed in this section of the manual.

9. If gas supply pressure is within normal range and no

adjustments are needed, proceed on to Step 11.

10. If the gas pressure is out of range, contact the gas utility,

gas supplier, qualifi ed installer or service agency to

determine the necessary steps to provide proper gas

pressure to the control.

11. Turn the power switch to the “OFF” position.

12. Shut off the gas supply at the manual gas valve in the gas

piping to the appliance.

13. Remove the manometer from the pressure tap on top of

the gas valve. On Models 400 - 501 re-tighten the set

screw inside the pressure tap. On Models 601 - 801

remove the 1/8" (3 mm) fi eld supplied fi tting and

reinstall the pipe plug removed in Step 3.

Check inlet gas supply

NOTICE

CSA or UL listed fl exible gas connections
are acceptable, but you must exercise
caution to ensure that the line has adequate
capacity to allow your boiler to fi re at full
rate. Consult with local codes for proper
installation or service procedures.

DO NOT adjust or attempt to measure gas
valve outlet pressure. Attempting to alter
or measure the gas valve outlet pressure
could result in damage to the valve, causing
potential severe personal injury, death, or
substantial property damage.

ƽ WARNING

Installation & Operation Manual