Vertical direct venting, Alternate vertical concentric venting – Lochinvar KNIGHT XL 801 User Manual
Page 34

34
5
Vertical direct venting
Alternate vertical concentric venting
This appliance may be installed with a concentric vent 
arrangement where the vent pipe is routed through an 
existing unused venting system; or by using the existing 
unused venting system as a chase for vent and combustion 
air routing.
Concentric Venting Arrangement
The venting is to be vertical through the roof. The annular 
space between the O.D. of the vent pipe and the I.D. of the 
existing unused venting system is utilized for the combustion 
air source.
The minimum size of the existing vent system required to 
achieve enough annular space for combustion air can be 
found in Table 5A.
The upper and lower termination as well as any other unsealed 
joints in the existing vent system must be sealed to ensure that 
all combustion air is drawn from under the vent cap as shown 
in FIG.’s 5-8 and 5-9.
Approved venting materials must be used as specifi ed in 
Table 3A on page 18.
Follow all vent / air termination and clearance requirements 
per this section to the appropriate example. Installation must 
comply with local requirements and with the National Fuel 
Gas Code.
The maximum allowable equivalent vent and air intake 
lengths for this venting arrangement are to be determined 
from the General Venting Section.
If an existing unused venting system is converted for use 
with this method of concentric venting, the installer must 
ensure that the existing venting system is clean and free from 
particulate contamination that will harm this appliance and 
cause increased nuisance calls or maintenance. See Table 1A 
on page 11 for a list of corrosive contaminants and sources.
Two example scenarios of a concentric venting arrangement 
are shown for illustrative purposes in FIG.’s 5-8 and 5-9.
Figure 5-8 Concentric Vent Example 1
12"
MIN.
FLUE EXHAUST
AIR INLET 
W/ SCREEN
FLUE OUTLET
SEALED 
CAP
EXISTING
SEAL
SEAL
COMBUSTION AIR
*For concept illustration only. Individual installations
may vary due to job site specifi c equipment.
Figure 5-9 Concentric Vent Example 2
FLUE EXHAUST
AIR INLET 
W/ SCREEN
FLUE OUTLET
SEALED
CAP
EXISTING
SEAL
SEAL
COMBUSTION AIR
SEAL
*For concept illustration only. Individual installations
may vary due to job site specifi c equipment.
Model
Vent / Air
Inlet Size
Minimum Existing
Vent / Chase Size
400 - 601
4"
7"
701 - 801
6"
10"
Table 5A Alternate Vertical Concentric Vent / Chase Sizes
Installation & Operation Manual
