Start-up – Lochinvar KNIGHT XL 801 User Manual
Page 60

60
Set domestic hot water (DHW) operation
Verify DHW mode
There are two (2) modes of operation for DHW. In Normal 
Mode, when a DHW demand begins, the control will start 
the DHW pump, turn off the boiler pump (if running), and 
modulate to bring the outlet temperature to the DHW boiler 
set point. The maximum fi ring rate may be limited in this 
mode if desired.
In Zone Mode it is assumed that the indirect DHW tank is 
piped as a zone on the primary loop. When a DHW demand 
begins, the control will turn on the DHW pump output, and 
raise the system temperature set point to the DHW boiler set 
point (if higher). The system pump and the boiler pump will 
be turned on. In this mode, any low temperature zones (such 
as radiant heating) may need additional controls to limit the 
water temperature sent to those zones.
Set DHW target temperature
When in the DHW Mode, the control will modulate to 
maintain the boiler outlet temperature or system supply 
temperature to a set point. This set point is set at the factory 
to 180°F. If a different set point is desired, the appropriate 
parameter in the control must be changed. See the Knight XL 
Service Manual for a detailed explanation of this procedure.
Set maximum DHW fan speed
If the rated input of the indirect tank is less than the 
maximum output of the boiler, change the maximum DHW 
fan speed setting to limit the boiler output accordingly, see 
the Knight XL Service Manual for a detailed explanation of 
this procedure.
NOTICE
The internal clock does not adjust for 
Daylight Savings Time and therefore, will 
require a manual adjustment.
Confi guration of the cascade
10
Start-up
7. Turn the NAVIGATION dial to adjust the minutes. Press 
 
the NAVIGATION dial.
8. Turn the NAVIGATION dial to adjust the month. Press 
 
the NAVIGATION dial.
9. Turn the NAVIGATION dial to adjust the date. Press the 
 NAVIGATION 
dial.
10. Turn the NAVIGATION dial to adjust the year. Press the 
 
RIGHT SELECT [SAVE] key.
11. Press the RIGHT SELECT [HOME] key.
Please note that the brackets ([]) denote 
screen status.
NOTICE
Set clock
When installed in a Cascade system, the individual controls must 
be programmed for cascade operation. This is accomplished by 
accessing the control parameters. 
Press the [MENU] key for at least fi ve (5) seconds. Input the 
Installer code as described in the Knight XL Service Manual. 
Once the control parameters have been accessed, use the 
NAVIGATION DIAL to select the Control Mode parameters. 
Press the NAVIGATION DIAL to access these parameters. 
Rotate the NAVIGATION dial to select the parameter “Cascade 
Address”. Press the NAVIGATION dial to access this parameter. 
Each appliance in the Cascade system must be programmed 
with its own address. The boiler designated as the Leader will 
have an address of 0. The remaining boilers in the Cascade 
will be Members and have addresses from 1 - 7. Rotate the 
NAVIGATION dial to select the appropriate address. Press 
the RIGHT SELECT [SAVE] key. If installing the boilers in an 
existing system, the new boilers should be programmed as the 
Leader and/or the higher number addresses.
Press the RIGHT SELECT [HOME] key to upload the address 
into the control. Repeat this procedure for all boilers in the 
Cascade, designating the Leader control and the Member 
controls.
Please note that the brackets ([]) denote 
screen status.
NOTICE
The SMART SYSTEM control has a built-in clock that it 
uses for its night setback feature and for logging events. This 
clock must be set when the boiler is installed, and anytime the 
boiler has been powered off for more than 4 hours. Use the 
following procedure to set the clock:
1. Press and hold the LEFT SELECT [MENU] key for at 
 
least 5 seconds.
2. The display changes to read [PASSWORD], 
 
with four (4) zeros below it.
3. Press the RIGHT SELECT [SAVE] key.
4. The display will then show a menu with the time and 
 
date and temperature unit.
5. Press the NAVIGATION dial twice.
6. Turn the NAVIGATION dial to adjust the hours. Press 
 
the NAVIGATION dial.
Installation & Operation Manual