Operating information – Lochinvar KNIGHT XL 801 User Manual
Page 64

64
11
Operating information
Outdoor reset operation, if used
Target temperature with outdoor reset
This feature improves the system’s effi ciency as the outdoor 
temperature warms up.
See the Knight XL Service Manual to change the settings.
Reset curve
The reset curves look at outdoor air temperature and adjusts 
the set points.
Cascade
When multiple boilers are installed, they can be wired 
together in a cascade sequence. A maximum of eight boilers 
can be controlled from a single control. In this application 
one boiler would be designated as the Leader control and all 
others would be designated as Member controls. If installing 
the boilers in an existing system, the new boilers should 
be programmed as the Leader and/or the higher number 
addresses. The Leader control can be programmed to use 
Lead/Lag or Effi ciency Optimization control methods.
Once the Leader boiler receives a call for heat from a room 
thermostat, BMS, or Modbus, the control will determine what 
the set point will be. If outdoor air reset is desired, connect 
the outdoor air sensor to the terminals on the Low Voltage 
Connection Board on the Leader boiler. The set point will be 
calculated based on the programmed reset curve parameters. 
See the Knight XL Service Manual to program the reset curve. 
If outdoor air reset is not desired, do not connect the outdoor 
air sensor. A fi xed temperature set point can be programmed 
into the control. See page 59 of this manual to program the 
set point. 
If the water temperature at the system supply sensor is less 
than the set point + the turn-off offset - the off-on differential, 
then the control will initiate a call for heat on the Cascade 
(see the Knight XL Service Manual for an explanation of 
the offset and differential). The Leader will energize the lead 
boiler on the Cascade. For a new startup this will be the 
Leader boiler.
DHW, Night Setback, and Ramp Delay operation with 
cascade
For normal mode DHW operation any boiler(s) in the Cascade 
can be selected to provide heat for a DHW call. Select a boiler to 
be designated as the DHW boiler. Connect the DHW thermostat 
or sensor to the terminals on the Low Voltage Connection 
Board marked for the corresponding device. When the boiler 
receives a DHW call, the Leader control will take that boiler 
out of the Cascade sequence. If another boiler is available, the 
Leader will start it up to take its place. 
The DHW boiler will adjust its set point to the programmed 
DHW set point and will adjust its fi ring rate to maintain this. 
Once the DHW call has been satisfi ed, the Leader control will 
place that boiler back into the Cascade sequence. 
Switching of the boiler between DHW operation and SH 
operation when there is a call for both does not occur in Cascade 
Mode. 
When DHW is programmed for Zone Mode, connect the DHW 
thermostat or tank sensor to the Leader boiler. When a DHW 
call is received, the Leader will modulate the entire Cascade to 
bring the system supply temperature up to the DHW boiler set 
point (if higher).
Night Setback operation of the boilers within the Cascade is 
available. Programming of the Night Setback will be done 
through the Leader boiler. Refer to the Knight XL Service 
manual for information regarding Night Setback.
Ramp Delay operation of the boilers as described in the Knight 
XL Service Manual is available when the boilers are part of a 
Cascade system. 
Sequence of the cascade
To equalize the run time of all boilers on the Cascade, the fi ring 
sequence will automatically be changed at set intervals. 
For the fi rst 24 hours after initializing the Cascade, the sequence 
will be changed every hour. After that the sequence will be 
changed once every 24 hours. The switching on/off sequence 
will be as follows:
DAY
SWITCHING ON SEQUENCE
Day 1
L-M1-M2-M3-M4-M5-M6-M7
Day 1 + 1 hour
M1-M2-M3-M4-M5-M6-M7-L
Day 1 + 2 hours
M2-M3-M4-M5-M6-M7-L-M1
If a boiler is used to heat an indirect DHW tank, it will 
automatically be given the lowest priority.
Low water cutoff protection
1. The SMART SYSTEM control module uses temperature
sensing of both supply and return areas of the heat 
exchanger. If the fl ow rate is too low or the outlet 
temperature too high, the control module modulates and 
shuts the boiler down. This ensures boiler shutdown in 
the event of low water or low fl ow conditions.
2. Some codes and jurisdiction may accept these integral
features of the control in lieu of requiring an additional 
limit control or low water cutoff. Consult local jurisdiction 
to determine. A low water cutoff is available from the 
factory (WTR20009).
Installation & Operation Manual
