General, Venting – Lochinvar KNIGHT XL 801 User Manual
Page 22
22
3
General
venting
If the boiler combustion air inlet
is located in a laundry room or
pool facility, for example, these
areas will always contain hazardous
contaminants.
To prevent the potential of severe
personal injury or death, check for
areas and products listed in Table 1A,
page 11 before installing the boiler or
air inlet piping.
If contaminants are found, you
MUST:
• Remove products permanently.
—OR—
• Relocate air inlet and vent
terminations to other areas.
ƽ WARNING
ƽ WARNING
Air contamination
Pool and laundry products and common household and hobby
products often contain fl uorine or chlorine compounds. When
these chemicals pass through the boiler, they can form strong
acids. The acid can eat through the boiler wall, causing serious
damage and presenting a possible threat of fl ue gas spillage or
boiler water leakage into the building.
Please read the information given in Table 1A, page 11,
listing contaminants and areas likely to contain them. If
contaminating chemicals will be present near the location of
the boiler combustion air inlet, have your installer pipe the
boiler combustion air and vent to another location, per this
manual.
Model Description
Kit
Number
400 - 801
Filter Box Assembly
KIT30022
90° Elbow with Screen
KIT30053
Table 3F Optional Room Air Kit
ƽ WARNING When utilizing the single pipe method,
provisions for combustion and ventilation
air must be in accordance with Air for
Combustion and Ventilation, of the
latest edition of the National Fuel Gas
Code, ANSI Z223.1, in Canada, the latest
edition of CGA Standard B149 Installation
Code for Gas Burning Appliances and
Equipment, or applicable provisions of the
local building codes.
Installation & Operation Manual