2. Features of W-3WAY ECO-i SYSTEM
2-1. Outline of W-3WAY ECO-i SYSTEM
System
example
ADDITION
CONCENTRATION
CONNECTION
Inverter unit
Inverter unit
If your indoor capacity load changes in the future,
it’s easy to add on both indoor and outdoor units
using the same piping.
*If the additional installment of outdoor and indoor units is
expected, the size of refrigerant piping should be decided
according to the total capacity after the addition.
If indoor/outdoor units need servicing, a ball
valve (optional) cuts off non-operational
units to let other units stay running.
* The capacity after the setting is
made must not exceed 32 PS.
Since all pipings are
concentrated into
one pipe shaft, you
can minimize piping
space and construc-
tion labor
Maximum number of combined outdoor units
Maximum horsepower of combined outdoor units
Maximum mumber of connectable indoor units
Indoor/outdoor unit capacity ratio
Maximum actual tubing length
Maximum level difference (when outdoor unit is lower)
Maximum total tubing length
2
32 HP
40
50~130%
492 ft
164 (131) ft
984 ft
System limitations
✟ Combination of outdoor units
The DC inverter unit can be used independently or in combination.
CAUTION
R407C models and R22 models must not be used in combination with each
other.
1
1
2
10
16
10
16
20
26
32
Total horse
power
Inverter unit
Combination of outdoor units
1
2
1
●
Solenoid
valve kit
Indoor unit