beautypg.com

Model selecting and capacity calculator – Sanyo CHDZ09053 User Manual

Page 17

background image

2-7

Design of W-3WAY ECO-i SYSTEM Unit Specifi cations

1

2

3

4

5

6

7

8

1. Model Selecting and Capacity Calculator

Liquid tubing size

Amount of refrigerant

(in. (mm))

charge (oz/ft.)

ш1/4"

(ш6.35)

0.279

ш3/8"

(ш9.52)

0.602

ш1/2"

(ш12.7)

1.38

ш5/8"

(ш15.88)

1.99

ш3/4"

(ш19.05)

2.78

ш7/8"

(ш22.22)

3.93

Table 2-5 Amount of Refrigerant Charge

Table 2-7 Refrigerant tubing (Existing tubing can be used.)

Tubing size (in. (mm))

Material

O

Material 1/2H • H

ш1/4" (ш6.35)

t1/32" (0.8)

ш7/8" (ш22.22)

t5/128" (1.0)

ш3/8" (ш9.52)

t1/32" (0.8)

ш1" (ш25.40)

t5/128" (1.0)

ш1/2" (ш12.7)

t1/32" (0.8)

ш1-1/8" (ш28.58)

t5/128" (1.0)

ш5/8" (ш15.88)

t5/128" (1.0)

ш1-1/4" (ш31.75)

t3/64" (1.1)

ш3/4" (ш19.05)

over t5/128" (1.0)

ш1-3/8" (ш34.93)

over t3/64" (1.15)

* When bending the tubes, use a bending

radius that is at least 4 times the outer

diameter of the tubes.

In addition, take sufficient care to avoid

crushing or damaging the tubes when

bending them.

ш5/8"

(ш15.88)

ш3/8"

(ш9.52)

ш3/8"

(ш9.52)

ш1/4"

(ш6.35)

ш1/2"

(ш12.70)

ш5/8"

(ш15.88)

ш3/4"

(ш19.05)

ш7/8"

(ш22.22)

ш5/8"

(ш15.88)

ш3/4"

(ш19.05)

ш3/4"

(ш19.05)

ш7/8"

(ш22.22)

ш1/2"

(ш12.70)

Total system horsepower

Suction tubing

Discharge tubing

Indoor unit type

7

9

12

18

24

36

48

Liquid tubing

Gas tubing

Liquid tubing

0.8

1.3

1

2

3

4

5

60

6

76

*1

8

96

*1

10

Distribution
joint –
solenoid valve
kit tubing

Solenoid valve
kit – Indoor
unit tubing
connection

*1: For the solenoid valve kits, use type 160 with parallel specifications. Branch the tubing before and after the solenoid valve kits.

Table 2-6 Indoor Unit Tubing Connection Size (

1

40

)

in. (mm)

This manual is related to the following products: