4-way air discharge semi-concealed type (xm type) – Sanyo CHDZ09053 User Manual
Page 146
4-22
W-3WAY ECO-i SYSTEM Unit Specifi cations
1
2
3
4
5
6
7
8
2. 4-Way Air Discharge Semi-concealed Type (XM Type)
Indoor unit (E)
MODEL No.
XMHX1252
Source
208 - 230 V / 1ø / 60 Hz
Controller P.C.B. Ass'y
CR-XM075XH (Microprocessor), POW-XM075XH
Fan...(Number diameter)
in. (mm)
Turbo (1...ш12-5/8 (ш322), L5-3/4 (L147))
Fan motor
Model...Nominal output
W
SIC-72FV-D866-1...66W
Source
280 / 340 V (DC) / 3 phase
No. of pole...r.p.m. (230V, High)
rpm
8P...540
Coil resistance
(Ambient temperature 68°F)
Ω
–
Run capacitor
VAC, µF
–
Safety device
fuse
Operating temperature
Open °F (°C)
285
+4
–5
(141
+2
–3
)
Electronic expansion valve
Coil
UKV-A054
Coil resistance (at 68°F)
Ω
ORG – GRY : 46
YEL – GRY : 46
RED – GRY : 46
BLK – GRY : 46
Valve body
UKV-18D31
Heat exchanger
Coil
Aluminum plate fin / Copper tube
Rows...fin pitch
in. (mm)
2...1/16 (1.4)
Face area
ft
2
(m
2
)
2.91 (0.27)
Panel
Model No.
PNR-XM185
Auto louver motor
MP24ZN-12V
Coil resistance (at 77°F)
Ω
380
Ω ± 7% / phase
Drain pump
PLD-12230ST-2
Rated
V, Hz, W
AC230V, 60Hz, 10.8W
Total head & capacity
in. (mm), gal/
min (cc/min)
33-1/2 (850), 0.11 (400)