beautypg.com

Concealed duct high-static pressure type (d type) – Sanyo CHDZ09053 User Manual

Page 186

background image

4-62

W-3WAY ECO-i SYSTEM Unit Specifi cations

1

2

3

4

5

6

7

8

5. Concealed Duct High-Static Pressure Type (D Type)

Indoor unit (B)

MODEL No.

DHX4852

Source

208 - 230 V / 1ø / 60 Hz

Controller P.C.B. Ass'y

CR-UXRP71B-B (Microprocessor)

Fan...(Number diameter)

in. (mm)

Centrifugal (1 ... ш7-5/8 (ш220))

Fan motor

Model...Nominal output

W

KFC4Q-401A6P...400W

Source

208 - 230 V / 1ø / 60 Hz

No. of pole...r.p.m. (230V, High)

rpm

4P... 1,077

Coil resistance

(Ambient temperature 68°F)

Ω

WHT – BRN : 11.05

WHT – VLT : 1.796

VLT – ORG : 1.002

ORG – YEL : 4.574

YEL – PNK : 7.699

Run capacitor

VAC, µF

440 VAC, 7.0 µF

Safety device

fuse

Operating temperature

Open °F (°C)

266 ± 9 (130 ± 5)

Close °F (°C)

181 ± 27 (83 ± 15)

Electronic expansion valve

Coil

UKV-U030E

Coil resistance (at 68°F)

Ω

ORG – GRY : 46

YEL – GRY : 46

RED – GRY : 46

BLK – GRY : 46

Valve body

UKV-30D33

Heat exchanger

Coil

Aluminum plate fin / Copper tube

Rows...fin pitch

in. (mm)

4...5 / 64 (2.0)

Face area

ft

2

(m

2

)

3.02 (0.281)

This manual is related to the following products: