Model selecting and capacity calculator – Sanyo CHDZ09053 User Manual
Page 20
2-10
Design of W-3WAY ECO-i SYSTEM Unit Specifi cations
1
2
3
4
5
6
7
8
WARNING
Always check the gas den-
sity limit for the room in
which the unit is installed.
1-7. Check of limit density
When installing an air conditioner in a room, it is neces-
sary to ensure that if the refrigerant gas accidentally
leaks out, its density does not exceed the limit level for
that room.
If the density could exceed the limit level, it is neces-
sary to provide an opening between the unit and the
adjacent room, or to install mechanical ventilation
which is interlocked with the leak detector.
(Total refrigerant charged amount: oz)
(Min. indoor volume where the indoor unit is installed: ft.
3
)
Limit density 0.3 (oz/ft.
3
)
The limit density of refrigerant which is used in this unit
is 0.3 oz/ft.
3
(ISO 5149).
The shipped outdoor unit comes charged with the
amount of refrigerant fixed for each type, so add it to
the amount that is charged in the field. (For the refriger-
ant charge amount at shipment, refer to the unit's
nameplate.)
Minimum indoor volume and floor area as against the
amount of refrigerant is roughly as given in the follow-
ing table.
CAUTION
Pay special attention to any
location, such as a basement,
etc., where leaking refrigerant
can accumulate, since refrig-
erant gas is heavier than air.
1. Model Selecting and Capacity Calculator
0
0
57
114
170
227
284
341
398
454
511
568
625
682
738
795
852
909
966
1022
1079
1136
0
500
1000
1500
2000
2500
3000
3500
4000
4500
5000
5500
6000
6500
7000
7500
8000
8500
9000
9500
10000
1000
500
1500 2000 2500 3000
Total amount of refrigerant
Min.
indoor v
olume
Min.
indoor floor area
(when the ceiling is 8.8 ft.
high)
ft.
3
ft.
2
oz
Range above
the density limit of
0.3 oz/ft.
3
(countermeasures
needed)
Range below
the density limit of
0.3 oz/ft.
3
(countermeasures
not needed)
Check of limit density