2-10

Design of W-3WAY ECO-i SYSTEM Unit Specifi cations

1

2

3

4

5

6

7

8

WARNING

Always check the gas den-
sity limit for the room in
which the unit is installed.

1-7. Check of limit density

When installing an air conditioner in a room, it is neces-
sary to ensure that if the refrigerant gas accidentally
leaks out, its density does not exceed the limit level for
that room.
If the density could exceed the limit level, it is neces-
sary to provide an opening between the unit and the
adjacent room, or to install mechanical ventilation
which is interlocked with the leak detector.

(Total refrigerant charged amount: oz)

(Min. indoor volume where the indoor unit is installed: ft.

3

)

Limit density 0.3 (oz/ft.

3

)

The limit density of refrigerant which is used in this unit
is 0.3 oz/ft.

3

(ISO 5149).

The shipped outdoor unit comes charged with the
amount of refrigerant fixed for each type, so add it to
the amount that is charged in the field. (For the refriger-
ant charge amount at shipment, refer to the unit's
nameplate.)

Minimum indoor volume and floor area as against the
amount of refrigerant is roughly as given in the follow-
ing table.

CAUTION

Pay special attention to any
location, such as a basement,
etc., where leaking refrigerant
can accumulate, since refrig-
erant gas is heavier than air.

1. Model Selecting and Capacity Calculator

0

0

57

114

170

227

284

341

398

454

511

568

625

682

738

795

852

909

966

1022

1079

1136

0

500

1000

1500

2000

2500

3000

3500

4000

4500

5000

5500

6000

6500

7000

7500

8000

8500

9000

9500

10000

1000

500

1500 2000 2500 3000

Total amount of refrigerant

Min.

indoor v

olume

Min.

indoor floor area

(when the ceiling is 8.8 ft.

high)

ft.

3

ft.

2

oz

Range above
the density limit of
0.3 oz/ft.

3

(countermeasures
needed)

Range below
the density limit of
0.3 oz/ft.

3

(countermeasures
not needed)

Check of limit density