3-23
Control of W-3WAY ECO-i SYSTEM
1
2
3
4
5
6
7
8
2. Wireless Remote Controller
2-17. Test Run Setting
1. Remove the receiver unit face plate, and set the DIP
switch to “Test Run - ON” position.
2. Run the air conditioner using the wireless remote control-
ler by pressing the “ON/OFF” button.
All LEDs (“RUN,” “TIMER” and “STANDBY”) blink during
test run operation.
No temperature control is effective with the wireless re-
mote controller in the “Test Run - ON” position.
To avoid mechanical strain on the air conditioner, do not
use this mode except for conducting a test run.
3. Select any one of the operation modes HEAT, COOL or
FAN for the test run.
*
The outdoor unit will not start running for about 3 min-
utes after the power ON button is pressed.
4. After the test run operation, stop the air conditioner using
the wireless remote controller, and then reset the DIP
switch in the receiver unit as it was before. (To prevent
constant test running of the air conditioner, the receiver
unit has a 60-minute off timer function.)