Model selecting and capacity calculator – Sanyo CHDZ09053 User Manual
Page 16
![background image](/manuals/153526/16/background.png)
2-6
Design of W-3WAY ECO-i SYSTEM Unit Specifi cations
1
2
3
4
5
6
7
8
32
249.100
26
ш7/8"
(ш22.22)
ш7/8"
(ш22.22)
ш1-1/8"
(ш28.58)
10
95.500
ш1/2"
(ш12.70)
153.600
16
ш1-1/8"
(ш28.58)
ш5/8"
(ш15.88)
10
10
191.000
20
ш3/4"
(ш19.05)
ш1-3/8"
(ш34.93)
10
16
16
16
ш3/4"
(ш19.05)
ш3/8"
(ш9.52)
307.200
16
10
Total system
horsepower
Combined
outdoor units
Suction tubing
Discharge tubing
Liquid tubing
BTU/h
ш3/4"
(ш19.05)
ш1-1/8"
(ш28.58)
ш1-3/8"
(ш34.93)
ш5/8"
(ш15.88)
ш1-1/8"
(ш28.58)
ш1/2"
(ш12.70)
ш1-1/8"
(ш28.58)
ш3/8"
(ш9.52)
ш7/8"
(ш22.22)
ш5/8"
(ш15.88)
ш5/8"
(ш15.88)
ш3/4"
(ш19.05)
ш5/8"
(ш15.88)
ш3/4"
(ш19.05)
ш3/4"
(ш19.05)
ш7/8"
(ш22.22)
ш3/8"
(ш9.52)
ш3/8"
(ш9.52)
ш3/8"
(ш9.52)
ш1/2"
(ш12.70)
–
238.900
(25 hp)
200.600
(21 hp)
24.200
(2.5 hp)
24.200
(2.5 hp)
85.300
(9 hp)
54.600
(6 hp)
54.600
(6 hp)
85.300
(9 hp)
258.000
(27 hp)
–
ш3/4"
(ш19.05)
ш1-1/8"
(ш28.58)
258.000
(27 hp)
238.900
(25 hp)
102.400
(11 hp)
ш1/2"
(ш12.70)
ш1-1/8"
(ш28.58)
ш3/4"
(ш19.05)
102.400
(11 hp)
124.200
(13 hp)
124.200
(13 hp)
Below BTU/h
Over BTU/h
143.300
(15 hp)
ш1/2"
(ш12.70)
ш1-1/8"
(ш28.58)
ш7/8"
(ш22.22)
ш7/8"
(ш22.22)
ш1-1/8"
(ш28.58)
143.300
(15 hp)
162.400
(17 hp)
ш5/8"
(ш15.88)
ш1-1/8"
(ш28.58)
162.400
(17 hp)
200.600
(21 hp)
Total capacity
after distribution
Tubing size
Suction tubing
Liquid tubing
Discharge tubing
hp = horsepower
Unit: in. (mm)
Below BTU/h
Over BTU/h
Total capacity
after distribution
Tubing size
ш1-3/8"
(ш34.93)
Suction tubing
Liquid tubing
Discharge tubing
ш7/8"(ш22.22)
ш7/8"(ш22.22)
ш3/8"(ш9.52)
ш3/8"(ш9.52)
95.500
153.600
ш3/4"(ш19.05)
ш1-1/8"(ш28.58)
Brazing connection
Brazing connection
Brazing connection
ш1/2"(ш12.7)
Flare connection
Suction tubing
Discharge
tubing
Balance tubing
BTU/h
Liquid tubing
Table 2-4 Outdoor Unit Tubing Connection Size (
A
–
D
)
Unit: in. (mm)
1-4. Tubing Size
1. Model Selecting and Capacity Calculator
Table 2-2 Main Tubing Size (LA)
Unit: in. (mm)
*1: If future extension is planned, select the tubing diameter based on the total horsepower after extension.
However extension is not possible if the resulting tubing size is two ranks higher.
*2: The balance tube (outdoor unit tube) diameter is ш3/8" (ш9.52).
*3: Type 1 tubing should be used for the refrigerant tubes.
*4: If the length of the longest tube (L1) exceeds 295 ft. (equivalent length), increase the main tube (LM) size by 1 rank for the
suction, discharge, and liquid tubes. (Use field-supply reducers.) (Select from Table 2-2 and Table 2-7.)
*5: If the longest main tube length (LM) exceeds 164 ft., increase the main tube size at the portion before 164 ft. by 1 rank for
the suction tubes and discharge tubes.
(For the portion that exceeds 164 ft., set based on the main tube sizes (LA) listed in the table above.)
*1: If the total capacity of the indoor units connected to
the tube ends is different from the total capacity of
the outdoor units, then the main tube size is selected
based on the total capacity of the outdoor units.
(For LA, LB, and LF in particular)
Table 2-3 Main Tubing Size After Distribution (LB, LC...)