beautypg.com

System design – Sanyo CHDZ09053 User Manual

Page 33

background image

2-23

Design of W-3WAY ECO-i SYSTEM Unit Specifi cations

1

2

3

4

5

6

7

8

15 to 30

B

A

B

A

Tube branching methods (horizontal use)

Arrow view

Horizontal
line

View as seen
from arrow

Ball valve

(BV: purchased

separately)

Main tubing

Types of vertical trap specifications

(If only 1 unit is connected, a ball valve
is also needed on this side.)

Indoor unit (1)

(When not using ball valve)

(When using ball valve)

Branch tubing is
directed upward.

(Each unit is connected
to tubing that is either
level or is directed
downward.)

Main tubing

Indoor unit

More than
7–7/8"

Indoor unit (more than 2 units)

Horizontal

Indoor unit is directed downward

Outdoor

Indoor

Indoor

Indoor

Solidly welded
shut (X)

Horizontal

line

Horizontal

line

L3 6.56 ft.

Install at a
positive angle

Install at a
positive angle
(15 – 30°)

Header joint system (Indoor)

2-3. Installing Distribution Joint

(1) Refer to “HOW TO ATTACH DISTRIBUTION JOINT”

enclosed with the optional distribution joint kit (APR-
CHRZP900BAB, RZP224BAB, RZP680BAB,
RZP1350BAB).

(2) When creating a branch using a commercially available

T-joint (header joint system), orient the main tubing so that
it is either horizontal (level) or vertical. In order to prevent
accumulation of refrigerant oil in stopped units, if the main
tubing is horizontal then each branch tubing length should
be at an angle that is greater than horizontal. If the main
tubing is vertical, provide a raised starting portion for each
branch.

[Header joint system]

Be sure to solidly weld shut the T-joint end (marked by “X”

in the fi gure). In addition, pay attention to the insertion
depth of each connected tube so that the fl ow of refrig-
erant within the T-joint is not impeded.

When using the header joint system, do not make fur-

ther branches in the tubing.

Do not use the header joint system on the outdoor unit

side.

(3) If there are height differences between indoor units or if

branch tubing that follows a distribution joint is connected
to only 1 unit, a trap or ball valve must be added to that
distribution joint. (When adding the ball valve, locate it within
15 - 3/4" of the distribution joint.)

If a trap or ball valve is not added, do not operate the
system before repairs to a malfunctioning unit are
completed. (The refrigerant oil sent through the tubing
to the malfunctioning unit will accumulate and may
damage the compressor.)

2. System Design

Pay special attention to any
location, such as a basement,
etc., where leaking refrigerant
can accumulate, since
refrigerant gas is heavier than
air.

CAUTION

This manual is related to the following products: