beautypg.com

Wireless remote controller – Sanyo CHDZ09053 User Manual

Page 65

background image

3-11

Control of W-3WAY ECO-i SYSTEM

1

2

3

4

5

6

7

8

2. Wireless Remote Controller

(1) To assign the wired remote controller as the sub unit,

locate the address connector at the rear of the wired
remote controller PCB and disconnect it. Reconnect it to
the sub unit position.

(2) To assign the wireless remote controller as the sub unit,

locate the dip switch [S003] on the wireless receiver unit
PCB. Set the No. 3 switch to the ON position.

2-5. How to use the Test Run Setting

1. Set DIP switch [S003] No. 1 on the wireless receiver unit

PCB from OFF to ON.

2. All indicator lamps in the display section blink during test

run operation.

3. No temperature control is available during the test run.

4. After the test run, be sure to reset DIP switch No. 1 back

to the OFF position and check that no indicator lamps
are blinking. Then remount and attach the PCB cover as
before.

To avoid placing excessive operating load on the equipment,
use this function only when conducting the test run.

NOTE

CN1

(optional)

(optional)

1 2

1 2

Indoor

unit

(sub)

(main)

Receiver unit

Remote controller
terminal board

Ground

Wireless remote

controller kit

Wired remote

controller

Remote control wiring (field supply)

When 1 indoor unit is operated with 2 remote controllers:

(The indoor unit runs according to which of the remote controllers is assigned as the main or sub unit.)

*

*

Use field wiring cables with a
cross-sectional area of at least
AWG#20 to AWG#14

* The maximum total length of

crossover cables must be no
longer than 1320 ft.

CN1

(optional)

1 2

1 2

(optional)

Indoor

unit No.1

Indoor

unit No.2

Indoor

unit No.3

Indoor

unit No.4

Receiver
unit

(Main)

(Sub)

When several groups of indoor units are operated with 2 remote controllers:

(The remote controller (main or sub unit) can operate with any indoor unit.)

Remote control
wiring among the
control groups
(field supply)

*

*

Ground

Ground

Ground

Ground

Fig. 3-5

*

Wireless remote

controller kit

Wired remote

controller

Remote controller
terminal board

Use field wiring cables with a
cross-sectional area of at least
AWG#20 to AWG#14

*

* The maximum total length of

crossover cables must be no
longer than 660 ft.

Fig. 3-6

Receiver PCB

Receiver unit
cover

ON

1

2

3

4

Adjustable
corner cap

S003
Bit 1: OFF ON

This manual is related to the following products: