Wireless remote controller – Sanyo CHDZ09053 User Manual
Page 65
3-11
Control of W-3WAY ECO-i SYSTEM
1
2
3
4
5
6
7
8
2. Wireless Remote Controller
(1) To assign the wired remote controller as the sub unit,
locate the address connector at the rear of the wired
remote controller PCB and disconnect it. Reconnect it to
the sub unit position.
(2) To assign the wireless remote controller as the sub unit,
locate the dip switch [S003] on the wireless receiver unit
PCB. Set the No. 3 switch to the ON position.
2-5. How to use the Test Run Setting
1. Set DIP switch [S003] No. 1 on the wireless receiver unit
PCB from OFF to ON.
2. All indicator lamps in the display section blink during test
run operation.
3. No temperature control is available during the test run.
4. After the test run, be sure to reset DIP switch No. 1 back
to the OFF position and check that no indicator lamps
are blinking. Then remount and attach the PCB cover as
before.
To avoid placing excessive operating load on the equipment,
use this function only when conducting the test run.
NOTE
CN1
(optional)
(optional)
1 2
1 2
Indoor
unit
(sub)
(main)
Receiver unit
Remote controller
terminal board
Ground
Wireless remote
controller kit
Wired remote
controller
Remote control wiring (field supply)
When 1 indoor unit is operated with 2 remote controllers:
(The indoor unit runs according to which of the remote controllers is assigned as the main or sub unit.)
*
*
Use field wiring cables with a
cross-sectional area of at least
AWG#20 to AWG#14
* The maximum total length of
crossover cables must be no
longer than 1320 ft.
CN1
(optional)
1 2
1 2
(optional)
Indoor
unit No.1
Indoor
unit No.2
Indoor
unit No.3
Indoor
unit No.4
Receiver
unit
(Main)
(Sub)
When several groups of indoor units are operated with 2 remote controllers:
(The remote controller (main or sub unit) can operate with any indoor unit.)
Remote control
wiring among the
control groups
(field supply)
*
*
Ground
Ground
Ground
Ground
Fig. 3-5
*
Wireless remote
controller kit
Wired remote
controller
Remote controller
terminal board
Use field wiring cables with a
cross-sectional area of at least
AWG#20 to AWG#14
*
* The maximum total length of
crossover cables must be no
longer than 660 ft.
Fig. 3-6
Receiver PCB
Receiver unit
cover
ON
1
2
3
4
Adjustable
corner cap
S003
Bit 1: OFF ON